Chapter 3 Deployment
Manual VIPA System SLIO
3-8
HB300E - FM - RE_050-1BB00 - Rev. 10/30
Byte Function
Possible values
0
Input frequency C0 track A
1
Input frequency C0 track B
2
Input frequency C1 track A
3
Input frequency C1 track B
02h: 100kHz
07h: 5kHz
03h: 60kHz
08h: 2kHz
04h: 30kHz
09h: 1kHz
06h: 10kHz
Other values are not permissible!
•
Input frequency
allows you to preset a filter for I1, I4, I5 and I8. With the
help of filters you may e.g. filter signal peaks at a blurred input signal.
Byte Bit 7 ... 0
0
Bit 5 ... 0: Interrupt behavior
Bit 0: 0 (fix)
Bit 1: 0 (fix)
Bit 2: Proc. interrupt overflow
Bit 3: Proc. interrupt underflow
Bit 4: Proc. interrupt
comparison value
Bit 5: Proc. interrupt
end value
Bit 7 ... 6:
0 (fix)
•
Setting the appropriate bit activates the associated process interrupt
Byte Bit 7 ... 0
0
Bit 5 ... 0: Counter function
000000b = Count endless
000001b = Once: forward
000010b = Once: backwards
000100b = Once: no main direction
001000b = Periodic: forward
010000b = Periodic: backwards
100000b = Periodic: no main direction
Bit 7 ... 6:
0 (fix)
Byte Bit 7 ... 0
0
Bit 2 ... 0: Comparison bit is set
(... when following condition is met)
000b = never
001b
=
Counter value
>=
comparison value
010b
=
Counter value
<=
comparison value
100b
=
Counter value
=
comparison value
Bit 3: Counter direction track B inverted
0 = No (not inverted)
1 = Yes (inverted)
Bit 7 ... 4:
0 (fix)
CHxx
Input frequency
INT_I/II
C0/C1:
Interrupt behavior
FCT_I/II
C0/C1:
Counter function
MODE2_I/II
C0/C1:
Counter mode 2
Summary of Contents for SLIO FM 050-1BB00
Page 1: ...VIPA System SLIO FM 050 1BB00 Manual HB300E_FM RE_050 1BB00 Rev 10 30 July 2010...
Page 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BB00 Rev 10 30...
Page 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BB00 Rev 10 30...
Page 56: ...Chapter 3 Deployment Manual VIPA System SLIO 3 24 HB300E FM RE_050 1BB00 Rev 10 30...