background image

INSTALLATION INSTRUCTIONS 
Hydrosense ID Addressable Water Detection System 

 

 

Document Part No. 3500039 Issue:01 

Page | 30 of 32 

 

 

19. Panel Specification Summary 

19.1. Recommended Cables 

All field wiring should be installed using a shielded twin core cable (ideally with a blue outer sheath to allow easy 

identification). The minimum cross sectional area should be 1mm although in the case of the detection loops this 
depends  upon  the  length  of  the  cable  and  the  number  and  type  of  devices  fitted.  Loop  length  calculators  for 

various cable types are available. Drain wires of any field wiring should be maintained throughout the length of 
the  cable  and  terminated  at  the  panel  via  brass  cable  glands.  Refer  to 

Section  4.1

  for  loop  earth  termination 

requirements. 

19.2. Sounder Load 

Panel  Sounder  -  Two  24  volt  sounder  circuits,  each  fused  with  a  1  Amp  self-resetting  electronic  fuse.  Each 
sounder circuit is monitored using reverse polarity and a 10 k

Ω

 ohm end of line resistor. 

19.3. Current Consumption  

1 loop panel current consumption    

130 mA (power fault) 

 

 

 

 

 

300 mA in alarm (no alarm load) 

2 loop panel current consumption   

195 mA  (power fault) 

 

 

 

 

 

370 mA in alarm (no alarm load)

 

I/O board current consumption  

 

20 mA (quiescent), up to 1A in full alarm 

8 way relay card current consumption 

10 mA (quiescent), 250 mA in full alarm 

6 way sounder card current consumption 

30 mA (quiescent), 260 mA in full alarm + sounder load 

4 way zone board current consumption 

70 mA (quiescent), 250 mA in full alarm

 

19.4. Power Supply 

Supply Voltage     

230 VAC nominal (+10% / 15%) 

Supply rating     

3 Amps.  

Battery Charger  

 Charges up to 9 Ah sealed lead acid batteries with temperature compensation 
over the range -5 to +50 degrees Celsius. 

 

Battery Type  

 

Two 12 V sealed lead acid 9 Ah maximum  

Output current split  

Battery 1 Amp max, load 2 Amps min. 

Battery low indication 

21V,  

Earth fault indication  

< 30 K

Ω

 +28 V or 0 V to earth.

 

19.5. Field Devices 

Vimpex   

 

127 devices per loop 

 

Per 1 loop panel    

127 ID Addressable modules 

Per 2 loop panel   

254 ID Addressable modules 

Sub-address total  

800 addresses and sub-address limit per panel. 

19.6. Water Leak / Alarm / Fault Relay Ratings (see also Section 12) 

All panel relay contacts are rated at 30 VDC and 1 Amp maximum.  
 

Under no circumstances should voltages or currents outside of these limits be connected.

 

19.7. Zones 

All panels have 16 Zonal LED indicators fitted. Care should be taken to ensure that no more than 32 devices will 
affected by a single short or break in any detection circuit. 

19.8. Remote Control Inputs (see also Section 16) 

Unmonitored  digital  inputs,  activated  when  connected  to  the  Remote  Control  0V  terminal  with  an  in  line 
resistance of less than 50 Ohms.  

 
Note:  Remote  control  inputs  must  be  restricted  by  the  Access  Level  requirements.  Therefore  it  should  not  be 

possible  to  remotely  reset,  silence  or  operate  the  alarm  devices  without  some  means  of  gaining  access  to  this 
function. 

19.9. Auxiliary 24 Volt Monitored Output (see also Section 15.1) 

Permanent 24 volt output protected by a 500 mA self-resetting electronic fuse, monitored for fuse failure. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for hydrosense IDAP-S-2-230

Page 1: ...Delivering a New Standard in Water Leak Detection Installation Instructions Issue 01 October 2018 By www acornfiresecurity com www acornfiresecurity com...

Page 2: ...ring the Panel Autolearn Initial Startup 12 8 3 Configuring the Panel from PC 13 9 Facilities Menu 14 10 Detection circuits 15 10 1 Fitting additional Detection Circuit Loop Card IDAP LEC 16 11 Panel...

Page 3: ...for Water Leak in Same Zone 23 16 1 14 Resound for Leak Detection in Other Zone 23 16 1 15 Hide Disablement Event for Active Delays 23 16 1 16 Delays Active on Initialisation 23 16 1 17 Ignore Global...

Page 4: ...19 3 Current Consumption 30 19 4 Power Supply 30 19 5 Field Devices 30 19 6 Water Leak Alarm Fault Relay Ratings see also Section 12 30 19 7 Zones 30 19 8 Remote Control Inputs see also Section 16 30...

Page 5: ...ub address 123 2 Three addresses from 800 available The sub addresses can be treated as if they were individual addresses i e each can be allocated to any zone given an individual address message and...

Page 6: ...mA Maximum Ripple Voltage 1 5 0 3 Volts Battery Type Genesis E NP 7 12 7Ah 12V Battery Charge Voltage 27 6 VDC nominal temperature compensated Battery Charge Current 0 7 Amps Battery Fuse 20mm 3 15A...

Page 7: ...screws holding the plate in position and then remove the complete circuit board and plate Hold the assembly by gripping the metal plate only and try to avoid touching the circuit board Place the plat...

Page 8: ...of devices used and should be calculated for each installation Cabling for sounder circuits should be sized according to sounder load and cable length but 1 5mm2 should suffice in the majority of cas...

Page 9: ...the mains terminal block to minimise the danger of them shorting to other parts of the equipment if they become disconnected The mains terminal block contains a F1 6A L250V fuse and must be replaced...

Page 10: ...onnel and should not be operated by the user under any circumstances Opening the front cover also gives access to the PC Connection Port for programming If the processor stops running or re boots for...

Page 11: ...s fuse that will rupture if excessive current is demanded from the battery by the control panel This fuse is labelled F4 and is located on the underside of the circuit board To replace the battery fus...

Page 12: ...de switch located behind the aperture in the bottom right corner of the plate to the left position using a small screwdriver or similar tool Then press the internal Reset switch that can be seen throu...

Page 13: ...to normal by re starting the panel by pressing the Reset switch located with the door open and to the right of the Fuse Fail LED 8 3 Configuring the Panel from PC To allow configuration from a PC it i...

Page 14: ...acilities Menu A number of facilities are provided which can only be reached at Access Level 2 or 3 Access Level 2 can be reached by entering the correct password a 4 digit number and pressing the ent...

Page 15: ...in the wiring all of the devices will still remain connected to the control panel In the case of a short circuit the short circuit isolators will isolate the faulty section of the wiring and the pane...

Page 16: ...stallation The additional Loop Card mounts on the left hand side of the main board and fits into two connectors labelled X7 and X8 There are two mounting pillars on the main board to which the additio...

Page 17: ...the sounders will operate at the end of the delay unless the panel is reset Activation of two or more devices producing a Water Leak action an input configured to override output delays will override...

Page 18: ...se ID panel 14 1 16 Channel I O Board ID SIO 16 The 16 channel I O boards can be individually configured using the Loop Explorer PC LE2 configuration utility to modify its operation in response to Ala...

Page 19: ...acts which default to Leak Detection and Fault actions The 4 way Zone Board is in effect a self contained 4 zone conventional control unit For full details of 4 way zone boards refer to manual 3500044...

Page 20: ...he full 500 mA capability of this output for instance would require an additional 15 Ah of battery capacity Ideally use of the Aux 24V Output should be restricted to powering a limited number of addit...

Page 21: ...em from the Aux 24V Output such as additional I O boards should be catered for by additional capacity using the same formula as above and adding the result to the calculated capacity required to maint...

Page 22: ...nel is mounted The panel name can be up to 15 characters long 16 1 2 Panel Address Hydrosense ID panels should always be set to address 1 16 1 3 Protocol Control panels are supplied as Hydrosense comp...

Page 23: ...brightness of the display when the panel is installed in darkened locations such as control rooms and ships bridges 16 1 12 Any 2 Devices to Bypass Delays Def Ring Mode Outputs Only When this option i...

Page 24: ...es is the INPUT ACTION and the following describes how the control panel will respond to each of these As mentioned previously because this is fundamentally a Water Leak detection system 16 2 1 Water...

Page 25: ...stored in the event log 16 2 9 Reset Action An input designated as Reset will not produce any visible effect at the control panel but will reproduce the action of the Reset Button on the panel i e re...

Page 26: ...on continuously when any sound alarm input is operated This normally applies to sounders and would normally be accompanied by the Def Ring Mode and Silenceable attributes Note Any output on the Hydros...

Page 27: ...nfiguring outputs with a combination of delays to some outputs and no delays to other outputs To start the stage two delay the Silence Alarm Acknowledge button must be pressed during the stage one del...

Page 28: ...nly Inputs in the selected zone that are not configured as Water leak event type will not contribute to a Zonal Cause Effect Cause Effects can also be used to disable any Outputs or groups of Outputs...

Page 29: ...ettings 18 1 Contrast Adjust The viewing angle contrast of the Hydrosense ID front panel display may be adjusted by turning the CONTRAST adjust potentiometer The contrast adjust potentiometer can be a...

Page 30: ...250 mA in full alarm 19 4 Power Supply Supply Voltage 230 VAC nominal 10 15 Supply rating 3 Amps Battery Charger Charges up to 9 Ah sealed lead acid batteries with temperature compensation over the ra...

Page 31: ...s start occurring from devices fitted at the other end of the loop Also excessive Loop Sounder Current will cause bad data faults to occur when the sounders are operated In general the user is unaware...

Reviews: