background image

INSTALLATION INSTRUCTIONS 
Hydrosense ID Addressable Water Detection System 

 

 

Document Part No. 3500039 Issue:01 

Page | 27 of 32 

 

 

16.3.3. Silenceable 

Silenceable is normally applicable to sounder outputs and ensures that the output switches off when the alarm is 
silenced/acknowledged by the front panel pushbutton or operation of an input that is configured as an Ack. Alarm 

(Acknowledge Alarm input) . 

Note:  Any  output  on  the  Hydrosense  ID  System  is  considered  as  a  sounder  if  the  “Silenceable”  and 

“Sound  Alarm”  Output  attributes  are  selected.  If  any  of  these  outputs  are  faulty  or  disabled,  the 
“Sounder  Fault/Disabled”  indicator  will  illuminate.    These  outputs  would  also  be  disabled  by  the 
“Disable All Sounders” menu option.

 

16.3.4. Alert 

An  alert  output  will  pulse  on  and  off  when  any  alert  input  is  operated.  This  normally  applies  to  sounders  and 

would  normally  be  accompanied  by  the  Def.  Ring  Mode  and  Silenceable  attributes  i.e.  a  sounder  output.  Note: 
Some devices do not support pulsing outputs. 

16.3.5. Stage One Delay 

Outputs  can  be  delayed  from  0  to  5  minutes  in  half-minute  steps  by  changing  the  default  delay  of  zero  to  the 

desired time delay setting. 

16.3.6. Stage two Delay 

If  the  output  is  “silenceable”,  the  stage  two-delay  option  becomes  available.  The  stage  two  delay  gives  an 
additional time before the output operates after the alarm is acknowledged during the stage one delay. 

Note:  Care  must  be  taken  when  configuring  outputs  with  a  combination  of  delays  to  some  outputs 
and  no  delays  to  other  outputs.  To  start  the  stage  two  delay,  the  “Silence  Alarm(Acknowledge 

button)” must be pressed during the stage one delay period. If outputs elsewhere on the system are 
configured with no output delays and are also configured as “Silenceable”, then these outputs will be 

silenced when the stage one delay is acknowledged.  

In  the  majority  of  systems,  the  delays  to  outputs  are  configured  to  all  sounder  outputs  to  allow  a 

variable search time and therefore this comment is not applicable. 

16.3.7. Zoning 

Each output can also be put into a zone or not as required. It is useful to put outputs into zones if the output is 
required to respond to Def. ring mode or is to be controlled by a Cause & Effect entry.  

Outputs that are not put into a zone and are configured to respond to “Def. ring mode” will always turn on with 
any Water Leak condition (i.e. Common Alarm). Care should be taken to ensure that no more than 32 devices 

should affected by a single short or break in any detection circuit. 

16.3.8. Location Text 

Finally, each output can be given a location address. As well as being useful in identifying devices with monitored 
outputs  and  additional  power,  for  fault  conditions,  the  location  address  can  be  useful  in  identifying  the  device 

when compiling Cause & Effects programmes. 

16.3.9. Tech Alarm 

A Tech Alarm Output will turn on continuously when any Tech Alarm Input is operated.  

16.3.10. Pre-alarm 

A Pre-alarm Output will turn on continuously when any pre-alarm Input is operated. 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for hydrosense IDAP-S-2-230

Page 1: ...Delivering a New Standard in Water Leak Detection Installation Instructions Issue 01 October 2018 By www acornfiresecurity com www acornfiresecurity com...

Page 2: ...ring the Panel Autolearn Initial Startup 12 8 3 Configuring the Panel from PC 13 9 Facilities Menu 14 10 Detection circuits 15 10 1 Fitting additional Detection Circuit Loop Card IDAP LEC 16 11 Panel...

Page 3: ...for Water Leak in Same Zone 23 16 1 14 Resound for Leak Detection in Other Zone 23 16 1 15 Hide Disablement Event for Active Delays 23 16 1 16 Delays Active on Initialisation 23 16 1 17 Ignore Global...

Page 4: ...19 3 Current Consumption 30 19 4 Power Supply 30 19 5 Field Devices 30 19 6 Water Leak Alarm Fault Relay Ratings see also Section 12 30 19 7 Zones 30 19 8 Remote Control Inputs see also Section 16 30...

Page 5: ...ub address 123 2 Three addresses from 800 available The sub addresses can be treated as if they were individual addresses i e each can be allocated to any zone given an individual address message and...

Page 6: ...mA Maximum Ripple Voltage 1 5 0 3 Volts Battery Type Genesis E NP 7 12 7Ah 12V Battery Charge Voltage 27 6 VDC nominal temperature compensated Battery Charge Current 0 7 Amps Battery Fuse 20mm 3 15A...

Page 7: ...screws holding the plate in position and then remove the complete circuit board and plate Hold the assembly by gripping the metal plate only and try to avoid touching the circuit board Place the plat...

Page 8: ...of devices used and should be calculated for each installation Cabling for sounder circuits should be sized according to sounder load and cable length but 1 5mm2 should suffice in the majority of cas...

Page 9: ...the mains terminal block to minimise the danger of them shorting to other parts of the equipment if they become disconnected The mains terminal block contains a F1 6A L250V fuse and must be replaced...

Page 10: ...onnel and should not be operated by the user under any circumstances Opening the front cover also gives access to the PC Connection Port for programming If the processor stops running or re boots for...

Page 11: ...s fuse that will rupture if excessive current is demanded from the battery by the control panel This fuse is labelled F4 and is located on the underside of the circuit board To replace the battery fus...

Page 12: ...de switch located behind the aperture in the bottom right corner of the plate to the left position using a small screwdriver or similar tool Then press the internal Reset switch that can be seen throu...

Page 13: ...to normal by re starting the panel by pressing the Reset switch located with the door open and to the right of the Fuse Fail LED 8 3 Configuring the Panel from PC To allow configuration from a PC it i...

Page 14: ...acilities Menu A number of facilities are provided which can only be reached at Access Level 2 or 3 Access Level 2 can be reached by entering the correct password a 4 digit number and pressing the ent...

Page 15: ...in the wiring all of the devices will still remain connected to the control panel In the case of a short circuit the short circuit isolators will isolate the faulty section of the wiring and the pane...

Page 16: ...stallation The additional Loop Card mounts on the left hand side of the main board and fits into two connectors labelled X7 and X8 There are two mounting pillars on the main board to which the additio...

Page 17: ...the sounders will operate at the end of the delay unless the panel is reset Activation of two or more devices producing a Water Leak action an input configured to override output delays will override...

Page 18: ...se ID panel 14 1 16 Channel I O Board ID SIO 16 The 16 channel I O boards can be individually configured using the Loop Explorer PC LE2 configuration utility to modify its operation in response to Ala...

Page 19: ...acts which default to Leak Detection and Fault actions The 4 way Zone Board is in effect a self contained 4 zone conventional control unit For full details of 4 way zone boards refer to manual 3500044...

Page 20: ...he full 500 mA capability of this output for instance would require an additional 15 Ah of battery capacity Ideally use of the Aux 24V Output should be restricted to powering a limited number of addit...

Page 21: ...em from the Aux 24V Output such as additional I O boards should be catered for by additional capacity using the same formula as above and adding the result to the calculated capacity required to maint...

Page 22: ...nel is mounted The panel name can be up to 15 characters long 16 1 2 Panel Address Hydrosense ID panels should always be set to address 1 16 1 3 Protocol Control panels are supplied as Hydrosense comp...

Page 23: ...brightness of the display when the panel is installed in darkened locations such as control rooms and ships bridges 16 1 12 Any 2 Devices to Bypass Delays Def Ring Mode Outputs Only When this option i...

Page 24: ...es is the INPUT ACTION and the following describes how the control panel will respond to each of these As mentioned previously because this is fundamentally a Water Leak detection system 16 2 1 Water...

Page 25: ...stored in the event log 16 2 9 Reset Action An input designated as Reset will not produce any visible effect at the control panel but will reproduce the action of the Reset Button on the panel i e re...

Page 26: ...on continuously when any sound alarm input is operated This normally applies to sounders and would normally be accompanied by the Def Ring Mode and Silenceable attributes Note Any output on the Hydros...

Page 27: ...nfiguring outputs with a combination of delays to some outputs and no delays to other outputs To start the stage two delay the Silence Alarm Acknowledge button must be pressed during the stage one del...

Page 28: ...nly Inputs in the selected zone that are not configured as Water leak event type will not contribute to a Zonal Cause Effect Cause Effects can also be used to disable any Outputs or groups of Outputs...

Page 29: ...ettings 18 1 Contrast Adjust The viewing angle contrast of the Hydrosense ID front panel display may be adjusted by turning the CONTRAST adjust potentiometer The contrast adjust potentiometer can be a...

Page 30: ...250 mA in full alarm 19 4 Power Supply Supply Voltage 230 VAC nominal 10 15 Supply rating 3 Amps Battery Charger Charges up to 9 Ah sealed lead acid batteries with temperature compensation over the ra...

Page 31: ...s start occurring from devices fitted at the other end of the loop Also excessive Loop Sounder Current will cause bad data faults to occur when the sounders are operated In general the user is unaware...

Reviews: