11. Testing the automatic gate system.
It is necessary to test all the accessories connected to the control unit, especially the safety devices such as the sensitive edges and photocells.
Remember that the photocells reverse the movement of the gate only during closing and the sensitive edges and/or internal photocells, if engaged
during opening, reverse the movement of the gate for 1.5 seconds, while if engaged when closing they fully re-open the gate.
12. Trimmer for adjustments.
Trimmer
Function
Description
Range
TR1 - DELAY Pause time
With Dip switch 1 ON, it adjusts the amount of time during
which the gate remains stationary before automatic closing.
From 1 to 130 seconds, maximum,
clockwise
TR2 - TORQ Motor torque
With Dip switch 8 OFF, it adjusts the motor torque.
From 20 to 100%, maximum,
clockwise
TR3 - SL
Deceleration speed
It adjusts the deceleration speed.
If turned completely clockwise, deceleration is excluded
From 0 to 100%, maximum, clock-
wise
13. Dip switch functions.
Num-
ber
Sta-
tus
Function
Description
DIP 1
OFF
Automatic closing disabled
-
ON
Automatic closing enabled
The open gate is
closed automatically after the pause time.
DIP 2
OFF
Operating logic: Opens-Stops-Closes-Stops
It modifies the operating sequence of inputs SEQ (sequential) and PED
(pedestrian) also via remote control.
ON
Operating logic: Opens-Closes
DIP 3
OFF
Courtesy function on photocell disabled
-
ON
Courtesy function on photocell enabled
Reduction to 5sec of the residual pause time after passing over photocells.
DIP 4
OFF
Collective operating logic disabled
-
ON
Collective operating logic enabled
When opening the gate ignores any controls and reloads the pause time
when on pause.
DIP 5
OFF
Pre-flashing disabled
-
ON
Pre-flashing enabled
3 seconds before the start of each movement, the flashing lamp begins to
flash.
DIP 6
OFF
Flashing controlled by the control unit.
It configures the output for flashing lamps without independent flashing.
ON
Flashing built into the flashing lamp.
It configures the output for flashing lamps with independent flashing.
DIP 7
OFF
Hammering disabled
-
ON
Hammering enabled
It generates instant hammering to hook (at the end of closing) or release
(at the beginning of opening) the electrical lock.
DIP 8
OFF
Force adjustment enabled.
Possibility of adjusting the force of the motors using trimmer TR2 TORQ.
ON
Force adjustment disabled.
Motor force at maximum. Trimmer TR2 TORQ disabled.
DIP 9
OFF
“Soft” start disabled
-
ON
“Soft” start enabled
It slows down the start of each movement.
DIP 10
OFF
P.OUT for 2
nd
radio channel.
It enables use of the 2
nd
remote control channel.
ON
P.OUT for safety device test.
It checks the operation of the safety devices if connected to +P.OUT.
DIP 11
OFF
Input P.IN normally open
For use on a possible open-only push button
ON
Input P.IN normally closed
For use on a possible sensitive edge
DIP 12
OFF
Sensitive edge
with electro-mechanical switch
It configures the type of sensitive edge. In only operates with DIP 11 ON
ON
Sensitive edge with resistive load 8.2 Kohm
35