Due Fili Plus telephone interface

5.11c  Main telephone numbers "in Extended mode" (888 30 C N)

A main telephone number can be associated with each call button C to call an internal tap-off of the telephone 

switchboard or a group of indoor stations or a fixed or mobile telephone line directly.

Each telephone number can consist of a maximum of 16 digits and each digit can be between 0 and 9 or ‚*‘ and ‚#‘.

•  Call the internal tap-off or the telephone number where the interface is connected on a telephone, wait for the 

call tone and the subsequent brief tones (three repeated brief tones)

•  Type in code 

888

•  Type in programming code 

30

•  Type in the index referred to the call button 

(

from 01 to 40

) you want to configure

•  Type in the 

external telephone

 number, the internal tap-off 

N

 (e.g. 21/22/...) or the group 

Gr of indoor 

stations

 (e.g. 440/441/...)

•  When you have finished typing in the number, wait at least 5“ and for the three confirmation tones otherwise if 

you hear a

•  brief tone and a long tone this means that programming has not been accepted.

At the end of the operations, proceed directly to a new programming or hang up the telephone.

5.12  Controls (888 77 M A PPP G)

In addition to managing entryphone calls, the interface envisages the management of M controls.
The controls can be activated directly during an entryphone communication or not.
Up to a maximum of 40 controls are envisaged, associated with codes from 10 to 49 respectively.

The interface has the following default control configurations:

•  Code 11: Self-start of master entrance panel

•  Code 12: activates the master entrance panel lock

•  Code 13: activates the relay with ID1

•  Code 14: activates the relay with ID2

•  Code 15: activates the relay with ID3

•  Code 16: activates the relay with ID4

•  Code 17: activates function F1 for the master entrance panel

•  Code 18: activates function F2 for the master entrance panel

•  Code 19: close call

N.B.

: During a call, the first 10 controls can also be activated using only keys 0 to 9 followed by #.

For the STA

NDARD mode only, 10 dedicated or common controls can be assigned to the 4 homes. To do this, you 

need to enable the control password (see paragraph below).

Each control can be associated with one of the following functions:

•  Call the internal tap-off or the telephone number where the interface is connected on a telephone, wait for the 

call tone and the subsequent brief tones (three repeated brief tones)

•  Type in code 

888

•  Type in programming code 

77

•  Type in the number of the control 

(

from 10 to 49

) you wish to configure

•  Type in the type of control 

A

•  Type in the address of the outdoor station or of the relay 

PPP

•  Type in

 0

A

DESCRIPTION

PPP

0

Output F1 of the Outdoor station

001..015

1

Output F2 of the Outdoor station

001..015

2

Relay

001..016

3

Outdoor Station Lock

001..015

7

Outdoor Station Power-on

001..015

Summary of Contents for Elvox 40164

Page 1: ...Installer manual 40164 Telephone interface for Due Fili Plus entryphones and video entryphones...

Page 2: ...g a telephone call 888 62 SQ 7 5 6 Wait time before dialling a telephone number 888 85 T 7 5 7 Manual or automatic answer 888 75 C 1 0 7 5 8 Changing the interface address 888 74 C PPP 8 5 9 Master ad...

Page 3: ...ce can only be installed in a vertical Due Fili Plus BUS and it has the same installation restrictions as any Due Fili Plus indoor station It envisages three operating modes depending on the requireme...

Page 4: ...em and check it is working properly Secure 40164 to a DIN rail mounting frame Cut off the electricity power supply to the video door entry system Connect the Line terminals to an internal tap off N of...

Page 5: ...g programming simply recall the interface and resume programming from the last code executed 3 2 EXTENDED mode In this mode the IDs of the master devices must under all circumstances be programmed in...

Page 6: ...ce in the switchboard mode configuring it with ID 202 Should this ID already be occupied by a 40510 you will have to use different numbering the numbers possible on the Due Fili system are 201 202 203...

Page 7: ...the call tone and the subsequent three brief tones Type in the control code M followed by The default control codes are Code 11 Self start of master entrance panel Code 12 activates the master entran...

Page 8: ...ay with ID1 Control 4 activates the relay with ID2 Control 5 activates the relay with ID3 Control 6 activates the relay with ID4 Control 7 activates function F1 for the master entrance panel Control 8...

Page 9: ...wish to configure Wait for the three confirmation tones otherwise if you hear a brief tone and a long tone this means that programming has not been accepted At the end of the operations proceed direct...

Page 10: ...ed directly to a new programming or hang up the telephone The default interface occupies IDs from 41 to 80 in the Extended mode 888 87 C PPP If these IDs already exist in the system the default interf...

Page 11: ...g tone this means that programming has not been accepted At the end of the operations proceed directly to a new programming or hang up the telephone 5 11b Secondary telephone numbers 888 29 C I N In S...

Page 12: ...an entryphone communication or not Up to a maximum of 40 controls are envisaged associated with codes from 10 to 49 respectively The interface has the following default control configurations Code 11...

Page 13: ...ode 1 to activate 0 to deactivate Type in the index referred to the call button C from 1 to 4 Type in the confirmation code 5 Wait for the three confirmation tones otherwise if you hear a brief tone a...

Page 14: ...ock control Outdoor Station 001 015 7 ATTEMPTED call from outdoor station Outdoor Station 001 015 8 Call from outdoor station Outdoor Station 001 015 Type in 1 Wait for the three confirmation tones ot...

Page 15: ...ce or in the presence of echoes generally the more interference there is on the line the longer the minimum recognition duration To define the parameters of the telephone line proceed as follows Call...

Page 16: ...nd a long tone this means that programming has not been accepted At the end of the operations proceed directly to a new programming or hang up the telephone By default the interface is configured to m...

Page 17: ...Input voltage 24 48 VDC Maximum absorbed current Standby 38 mA Calling 50 mA Ring signal recognised 35Veff 25Hz 50Hz Busy tone recognition Frequency 425Hz 5Hz minimum tone duration 300ms DIGITAL BUS I...

Page 18: ...r waste The user must therefore hand the equipment at the end of its life cycle over to the appropriate municipal centres for the differentiated collection of electrical and electronic waste As an alt...

Page 19: ...17 Due Fili Plus telephone interface...

Page 20: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 49401684A0_MI_IT 02 2107...

Reviews: