Three simple push buttons and actuator with  8 A change-over 

relay output, to be completed with interchangeable 1 or - 3 

module buttons.

Device to be used as three single buttons or one single and one double, depending on the button. The 
push button can be configured independently from the relay too. The push button can only be pressed 
at the bottom.

CHARACTERISTICS.

•  Rated supply voltage: BUS 29 V
•  Input: 16 mA
•  Changeover relay output 
•  Controllable loads at 120-230 V~ (contact NO):
-  resistive loads:             8 A (20.000 cycles)
-  incandescent lamps: 8 A (20.000 cycles) 
-  fluorescent lamps and energy saving lamps: 1 A (20.000 cycles)
-  electronic transformers: 4 A (20.000 cycles)
-  ferromagnetic transformers: 8 A (20.000 cycles)
•  Controllable loads at 120-230 V~ (contacts NC and NO):
-  motors cos ø 0.6: 3,5 A (100.000 cycles)
• Button: 1 double, 1 single or 3 single ones.
•  Terminals: TP BUS, relay contacts (NO, C, NC)
•  Possible functions:
-  state reversal (step-by-step)
- button
-  control ON only
-  control OFF only
-  scenario activation.
• 

Consist with By-me flush and surface mounting control units, rel.2.0 and next and By-me 

2-module control units, rel. 2.0 and next.

CONFIGURATION.

FOR THE OPERATIONS OF INSTALLATION AND CONFIGURATION, SEE THE By-me SYSTEM 
INSTRUCTIONS MANUAL ATTACHED TO THE CONTROL UNIT.

Configuration must be done with the device without the key to be able to press the central configura-
tion button. The device can be used as three single buttons or one double push-button and a single one.
•  Functional blocks: 4 (3 buttons, 1 relay), each functional block can belong to at most 4 groups.
•  Selecting the functional block (configuration): during group creation, when the control unit requires 

pressing the device button: 

-  press the configuration button;
-  if the device must be configured as three single push-buttons, within 3 s, press the  right-hand 

button to select the right functional unit, the middle button to select the middle functional unit or the 
left-hand button to select the left functional unit; the red LED illuminates. If none of the three buttons 
is pressed within approximately 3 s the red LED will light up; in this case the functional block selected 
is the 4th, referring to the actuator.

-  if the device must be configured used as a double and a single push-button, proceed as follows:
• configure the left functional unit in the case in which you want a push-button with two modules on 

the left of the device (left middle button) and then configure the right functional unit (right 
button);

• configure the middle functional unit in the case in which you want a push-button with two modules 

on the right of the device (middle right button) and then configure the left functional unit 
(left button). 

-  with the red LED on, the control unit will configure the functional block; at the end of this operation 

the red LED will go out.

  When the device is not configured, the actuator is controlled by the left-hand button and can already be used.

PARAMETERS.

•  For the functional blocks related to the tree buttons it is possible to set the operating mode:
-  simple button (ON when pressed, OFF when released);
-  ON/OFF button (step-by-step);
-  button ON only;
-  button OFF only;
-  scenario control.
•  LED parameters:
-  LED off;
-  LED with normal operation (on if the associated actuator is ON);
-  LED with reverse operation;
-  LED always on for location in the dark.
-  central LED with normal operation (Double button);
-  central LED with reverse operation (Double button);
-  central LED always on for location in the dark (Double button).
  If the functional block belongs to more than one group, the “LED with normal operation” and “LED 

with reverse operation” parameters are not available. In these cases the control is confirmed by a 
LED status change for 3 s.

  If a double key is used, it is necessary to set the central LED behaviour to make the status visible. 
   In this case, configure the left button if the double button is on the left of the device or the middle 

button if the double button is on the right.

•  Functional block 4, related to the relay (see figure 1):
-  one- or two-position stable operation;

-  on delay and off delay: a value between 0 and 200 gives the time in seconds, a value between 201 

and 250 gives the time in minutes (for example 201 = 1 minute, 202 = 2 minutes, etc.);

  Monostable operation.
  On delay: delay in closing the NO contact of the relay from receiving the close command.
  Off delay: time for which the relay has the NO contact closed.
  Bistable operation.
  On delay: delay in closing the NO contact of the relay from receiving the ON command.
  Off delay: delay in opening the NO contact of the relay from receiving the OFF command.
 Note.
  If a group is created with a number of relays in one-position stable mode, set for all the same on and 

off delays and do not insert any other types of actuator in the same group; in this way, it is possible to 
have the status of the one-position stable relay indicated on the control button. For special require-
ments it is possible to use the group depth (for example to switch on two-position stable relays or 
dimmers with a single button).

• Default parameters: the two keys are enabled as a dimmer control and LED in normal operation; 

relay set on two-position stable operation with null on and off delay. The buttons are set as ON/OFF 
push-buttons (step step) and LED in normal operation.

SCENARIOS.

Each simple button can be dedicated to activating one scenario. The actuator can belong to multiple 
scenarios and, for each one of them, save the status to retrieve when activating the scenario. For 
further details see the control panel manual 

INSTALLATION RULES.

Installation should be carried out observing current installation regulations for electrical systems in the 
country where the products are installed.
The feeding circuit of the relay output must be protected against overloads by a device, fuse or auto-
matic circuit breaker, with rated current not higher than 10 A. For further instructions, please see the 
manual attached to the control panel.

CONFORMITY.

LV directive
EMC directive
Standard EN 50428

FIGURE 1.

FRONT VIEW.

BACK VIEW.

Terminals bus TP

Retard

d’activation

Retard de désactivation

Commande

ON

Retard

d’activation

Commande

ON

Retard de

désactivation

Commande

OFF

ACTIVATION

DÉSACTIVATION

MONOSTABLE

BISTABLE

 

Configuration button

120-230

NO

C

NC

Led

Eikon

20545

Arké

19545

Idea

16985

Plana

14545

Summary of Contents for by-me Eikon 20545

Page 1: ...lta pulsador de ON OFF paso paso pulsador sólo ON pulsador sólo OFF mando para escenario Parámetros del led led inhabilitado led con funcionamiento normal encendido si el actuador asociado está en ON led con funcionamiento invertido led siempre encendido para la identificación en la oscuridad led central con funcionamiento normal Tecla doble led central con funcionamiento invertido Tecla doble led...

Page 2: ... μπουτόν μόνο OFF έλεγχος σεναρίου Παράμετροι led led απενεργοποιημένο led με κανονική λειτουργία αναμμένο εάν ο επισυνδεδεμένος εκκινητής είναι στο ON led με ανεστραμμένη λειτουργία led πάντοτε αναμμένο για επισήμανση στο σκότος κεντρικό με κανονική λειτουργία Διπλό πλήκτρο led κεντρικό με ανεστραμμένη λειτουργία Διπλό πλήκτρο led κεντρικό πάντο τε αναμμένο για επισήμανση στο σκότος Διπλό πλήκτρο...

Page 3: ...ione OFF al rilascio pulsante ON OFF passo passo pulsante solo ON pulsante solo OFF comando scenario Parametri led led disabilitato led con funzionamento normale acceso se l attuatore associato è in ON led con funzionamento invertito led sempre acceso per individuazione al buio led centrale con funzionamento normale tasto doppio led centrale con funzionamento invertito tasto doppio led centrale se...

Page 4: ...ons it is possible to set the operating mode simple button ON when pressed OFF when released ON OFF button step by step button ON only button OFF only scenario control LED parameters LED off LED with normal operation on if the associated actuator is ON LED with reverse operation LED always on for location in the dark central LED with normal operation Double button central LED with reverse operatio...

Page 5: ... au relâchement bouton ON OFF pas à pas bouton seulement ON bouton seulement OFF commande situation Paramètres led led invalidée led avec fonctionnement normal allumée si l actuateur associé est sur ON led avec fonctionnement inversé led toujours allumée pour individualisation dans le noir led centrale avec fonctionnement normal Touche double led centrale avec fonctionnement inversé Touche double ...

Page 6: ... nur OFF Steuerung Szenarium LED Parameter LED deaktiviert LED auf normalem Betrieb an wenn zugeordnetes Stellglied auf ON LED mit invertiertem Betrieb LED immer an zur Lokalisierung im Dunkeln Zentral LED auf Normalbetrieb Doppeltaste Zentral LED auf invertiertem Betrieb Doppeltaste Zentral LED immer an zur Lokalisierung im Dunkeln Doppeltaste Falls der Funktionsblock mehr als einer Gruppe angehö...

Reviews: