6.3 Access levels
2 access levels are available: a user level and an installer level.
USER level enables:
• checking of the active system operating mode,
•
control of the fan’s On and Off settings (in the absence of a priority command),
• setting of the date and time,
•
checking of the following values:
-
Air pressure and volume,
-
The % of the fan’s max. speed,
-
Depending on the sensors wired to the RMEC controller, the level of CO2, temperature, level of hygrometry,
• alarm reporting.
INSTALLER levels enables:
•
modification of the operating mode,
• setting of the COP and CAV mode settings,
•
configuration of the VAV operating mode:
-
definition of the sensors used,
-
setting of the desired min. and max. measurement ranges,
-
setting of min. and max. air volume settings,
•
configuration of the clock function,
•
configuration of the power meter,
• access to the state of the RMEC inputs/outputs for diagnostics.
To access installer level, follow the instructions, below.
SYSTEM
CONFIGURATION
ACCESS CODE
: 0000
The value to set flashes
ACCESS CODE
: _000
Set each value to
1
ACCESS CODE
: 1,000
Confirm each value to move on to the following value
up to
1111
ACCESS CODE
: INSTALLER
Access to the INSTALLER main menu