NT00000603-JBRB-ECOWATT-PR-AN-191202
5. ELECTRICAL CONNECTION
5.1 Prior precautions
Models 30 to 92:
This electronic-switching motor cannot be powered directly by mains power, on pain of destruction. Its
power must be supplied by the controller. The device must be turned on and off via the RMEC local con
-
trol (wiring, see §"6.6 Local On/Off control (factory setting)", page 27) or via the BCCA external On/Off
control (wiring, see "5.4 Electrical connection of an external On / Off control", page 17). Do not turn off
the device by directly shutting off the controller’s power supply via the INTZ or shutting off the mains power
supply.
Shut off and disconnect the power supply before carrying out any work.
In case of work on the fan, the local on-off switch defined according to IEC947-3/695-2-1 must be open
and locked in this position (according to NF C 15-100).
5.2 Electrical features
Size
Single-phase 230V
Three-phase 400V
Input power
(kW)
Max. C.
(A)
Input power
(kW)
Max. C.
(A)
JBRB ECOWATT
®
PR 04
0.07
0.7
-
-
JBRB ECOWATT
®
PR 06
0.13
1.0
-
-
JBRB ECOWATT
®
PR 10
0.15
1.2
-
-
JBRB ECOWATT
®
PR 22
0.35
1.6
-
-
JBRB ECOWATT
®
PR 30
0.60
2.6
0.60
1.2
JBRB ECOWATT
®
PR 38
0.70
3.1
0.70
1.3
JBRB ECOWATT
®
PR 48
0.72
3.1
0.72
1.5
JBRB ECOWATT
®
PR 70
1.24
5.4
1.24
2.6
JBRB ECOWATT
®
PR 82
1.40
6.0
-
-
JBRB ECOWATT
®
PR 92
-
-
1.70
3.5
5.3
Electrical connection of the local on-off switch
The switch is used to isolate the device from the power supply in case of maintenance, or to turn the device
on/off.
JBRB ECOWATT
®
PR 04 to 22 Single-phase
N L