ViM JBRB ECOWATT PR Instruction Manual Download Page 1

NT00000603-JBRB-ECOWATT-PR-AN-191202

INSTRUCTION MANUAL
INSTALLATION | WIRING | COMMISSIONING | MAINTENANCE |

AFNOR CERTIFICATION

ISO 14001

Environnement

AFNOR CERTIFICATION

I S O   9 0 0 1

Q u a l i t é

JBRB ECOWATT

®

 PR

Collective residential building controlled mechanical ventilation 

Tertiary premise ventilation 400°C 1/2hr C4 approved

Efectis certificate: EFR-16-002341

Summary of Contents for JBRB ECOWATT PR

Page 1: ...MMISSIONING MAINTENANCE AFNOR CERTIFICATION ISO 14001 Environnement AFNOR CERTIFICATION ISO 9001 Q u a l i t JBRB ECOWATT PR Collective residential building controlled mechanical ventilation Tertiary...

Page 2: ...connection of a CENE power meter optional accessory 24 6 COMMISSIONING 24 6 1 Description of RMEC controller keys 24 6 2 Calibration of built in pressure sensors COMPULSORY STEP 24 6 3 Access levels 2...

Page 3: ...potentially explosive atmosphere Low salinity atmosphere without corrosive chemical agents 1 2 Safety instructions Put on appropriate PPE Personal Protective Equipment before any work Before installin...

Page 4: ...izes 48 to 92 High performance galvanised steel backward fan INTZ installed wired lockable safety switch ECM direct current motor outside airflow 04 to 22 IP44 class B single phase 230V 50Hz 30 38 48...

Page 5: ...fault on the unit when it leaves the factory with a pressure set point of 140Pa 0 Airflow m3 h Pressure Pa Regulated pressure setpoint Max airflow curve Regulated pressure curve CAV mode Constant air...

Page 6: ...point 120 240 360 480 600 720 840 960 1080 1200 10 0 20 30 40 50 60 70 80 90 100 The signal can be transmitted by different types of sensors SCO2 CO2 sensor 0 10V or 4 20mA in this case it will be dis...

Page 7: ...20 40 60 80 100 100 200 300 400 500 100 P W abs 100 0 0 100 50 100 150 200 300 400 500 600 700 Qv m3 h P W abs JBRB ECOWATT PR 10 COP JBRB ECOWATT PR 22 COP P Pa stat 0 100 200 300 400 500 0 200 400...

Page 8: ...0 1000 1500 2000 2500 3000 3500 100 0 500 1000 1500 2000 2500 3000 3500 4000 4500 0 100 200 300 400 500 600 700 800 P W abs Qv m3 h JBRB ECOWATT PR 48 COP JBRB ECOWATT PR 70 COP P Pa stat 0 100 200 30...

Page 9: ...1000 1200 1400 1600 1800 2000 3 INSTALLATION 3 1 Dimensions and weight JBRB ECOWATT PR 04 06 10 22 30 38 Horizontal discharge L M configuration A C D1 D1 B C I J B B C G H B E F Sense of the air Sens...

Page 10: ...3 365 473 365 121 JBRB ECOWATT PR 82 1 404 1 100 1 175 970 710 846 1 032 518 405 518 405 170 JBRB ECOWATT PR 92 1 404 1 100 1175 970 710 846 1 032 518 405 518 405 171 IS version 27mm JBRB ECOWATT PR 1...

Page 11: ...32 518 340 518 405 200 IS version 27mm JBRB ECOWATT PR 04 06 10 22 30 38 Vertical discharge L M configuration A C D1 B C B B C G H B F I E J Sense of the air Sense of the air Only available on modular...

Page 12: ...75 121 JBRB ECOWATT PR 82 1 358 1 100 1 175 970 710 846 1 032 518 405 482 415 170 JBRB ECOWATT PR 92 1 358 1 100 1 175 970 710 846 1 032 518 405 482 415 171 IS version 27mm JBRB ECOWATT PR 10 22 38 Ve...

Page 13: ...H I J Weight kg JBRB ECOWATT PR 48 1 444 1 105 800 560 450 990 918 433 270 320 340 135 JBRB ECOWATT PR 82 1 767 1 237 970 710 560 1 016 1 032 518 340 482 415 200 JBRB ECOWATT PR 92 1 767 1 237 970 710...

Page 14: ...ECOWATT PR 04 to 38 Ceiling mounted installation 100 C C JBRB ECOWATT PR Sigfox size 04 to 38 units can be installed with the cover facing downwards Air space of at least 100mm must be main tained bet...

Page 15: ...90 doubleaspiration 90 M Orientation rejet horizontal Orientation rejet vertical Enligne L Doubleaspiration D Modulablecoud 90 doubleaspiration 90 M Orientation rejet horizontal Orientation rejet ver...

Page 16: ...ect the power supply before carrying out any work In case of work on the fan the local on off switch defined according to IEC947 3 695 2 1 must be open and locked in this position according to NF C 15...

Page 17: ...5 4 Electrical connection of an external On Off control The RMEC controller has a local On Off control an external On Off control can be connected to terminals DI1 and GND The external on request tak...

Page 18: ...R1B R2B L1 L2 Ventilation fault wiring Open contact Stop of the fan 5 5 2 Relay electrical connection Model 30 to 82 single phase 1 2 3 4 Ventilation fault wiring Open contact Stop of the fan 5 6 7 8...

Page 19: ...80 relative humidity It can be connected to the RMEC in two ways according to use Temporary connection Standard application case for configuration of the product when the RMEC display is not clearly v...

Page 20: ...AT 12V GND terminals Finally tighten the cable gland to ensure the cable is securely fastened and main tain the RMEC s IP55 protection index Fasten the remote control to the wall may be built in to be...

Page 21: ...OG INPUTS 230V power supply REMOTE CONTROL POWER SUPPLY OUTPUTS POWER SUPPLY OUTPUTS DIGITAL INPUTS ANALOG OUTPUTS RELAYS PRESSURE SENSORS PA PB R1A R2A R1B R2B 22 32 44 21 31 43 11 12 0 LS HS BCCA 2V...

Page 22: ...D 15V AI2 GND 10V DI1 DI2 GND DI3 GND DI4 AO1 GND AO2 ANALOG INPUTS 230V power supply REMOTE CONTROL POWER SUPPLY OUTPUTS POWER SUPPLY OUTPUTS DIGITAL INPUTS ANALOG OUTPUTS RELAYS PRESSURE SENSORS PA...

Page 23: ...AI2 GND 10V DI1 DI2 GND DI3 GND DI4 AO1 GND AO2 5 9 Electrical connection of a potentiometer optional accessory The unit can operate in VAV mode airflow control setting by analogue input For this ope...

Page 24: ...RMEC controller keys Home page Function access keys JBRB ECOWATT XX RMEC VX X Confirm to access the main level menu Escape retour Ok Validation D filement s lection D filement s lection Several press...

Page 25: ...ng INSTALLER levels enables modification of the operating mode setting of the COP and CAV mode settings configuration of the VAV operating mode definition of the sensors used setting of the desired mi...

Page 26: ...t can be turned on and off in the following ways by order of priority 1 By the SMOKE EXTRACTION function The DI2 smoke extraction input always has priority over other controls 2 By the built in CLOCK...

Page 27: ...CONTROL ON The fan must start up To stop the fan repeat the same steps and select OFF 6 7 Selection of the main operating mode The unit can operate in different operating modes To select the desired o...

Page 28: ...nstant air volume despite network pressure drop changes The airflow setting is set at the factory according to unit sizes see table below PRODUCT AIRFLOW JBRB ECOWATT PR 04 224m3 h JBRB ECOWATT PR 06...

Page 29: ...d as follows DI3 input configuration Setting of 2 airflow set points Settings possible at installer level only 6 3 Access levels page 25 6 10 1Configuration on DI3 input as airflow setting Default scr...

Page 30: ...1800 2000 120 240 360 480 600 720 840 960 1080 1200 SCO2 maxi measurement SCO2 mini measurement Max measurement selected Mini measurement selected Mini desired airflow Maxi desired airflow Overall sen...

Page 31: ...the switch inside the RMEC controller MUST be set to the correct position see 5 8 Electrical connection of a sensor optional accessory page 22 SYSTEM CONFIGURATION 6 x 5 SENSOR CONFIG ANALOGUE INPUTS...

Page 32: ...ALOG INPUT 1 min CO2 0ppm Set the right value for the sensor used ANALOG INPUT 1 min CO2 100ppm Example P513 ANALOG 1 max CO2 VAL ANALOG INPUT 1 max CO2 2 000ppm Set the right value for the sensor use...

Page 33: ...27 with the following TEMPERATURE C HYGROMETRY in P528 ANALOG 1 min TEMP RANGE ANALOG INPUT 1 min 0 C ANALOG INPUT 1 min 10 C Example P529 ANALOG 1 max TEMP RANGE ANALOG INPUT 1 max 50 C ANALOG INPUT...

Page 34: ...60m3 h and 1 080m3 h between 2V and 5 5V 0 Maxi measurement selected Mini measurement selected Mini desired airflow Maxi desired airflow Voltage delivered by the potentiometer V Airflow m3 h Overall v...

Page 35: ...ple P534 ANALOG 1 max POTENTIOMETER RANGE ANALOG INPUT 1 max 10 0V Set the desired value ANALOG INPUT 1 max 5 5V Example 6 12 3Select the min airflow and max airflow settings SYSTEM CONFIGURATION 6 x...

Page 36: ...are allocated to one of the two cycles e g cycle 1 for week days and cycle 2 for weekends The Clock function is configured in 5 stages Step 1 by cycle definition of number of slots Step 2 by cycle def...

Page 37: ...YCLE1MODE CAV Example Example given for CYCLE1 To modify CYCLE2 replace the P107 steps with the following P141 CYCLE2 OPERATINGMODE CYCLE2MODE COP Set to desired operating mode CYCLE2MODE CAV Example...

Page 38: ...m P152 to P157 Slot 3 Cycle 1 Set point according to mode from P126 to P131 Slot 3 Cycle 2 Set point according to mode from P160 to P165 SYSTEM CONFIGURATION 2 x 1 CONFIGURATION CLOCK 7 x P110 CYCLECY...

Page 39: ...GURATION 5 x 4 ON OFF AND DIGIT INPUT CONFIG P426 DI4DIGIT INPUTS CONFIG QUICK INPUT WITHOUT Set on POWER METER QUICK INPUT POWER METER 6 14 2Set number of impulses per kWh transmitted by the meter us...

Page 40: ...ill present this fault menu automatically pops back up if a key is not pressed for 3 minutes In case of a problem with the displayed date time see 6 4 Setting of date and time page 26 7 MENU AND MODBU...

Page 41: ...cimal 0x0002 Two 16 bit registers to read For reading of a 4 byte setting specify a 32 bit register to read i e two 16 bit registers to read 0x04 size of data to write number of bytes 0x1F40 LSB16 val...

Page 42: ...00 e g 50 5 0 V R 1 byte 10 ALARMS Problem with built in AP sensor 0 no fault 1 fault R 1 byte 1 008 Problem with built in low pressure sensor 0 no fault 1 fault R 1 byte 1 012 Set point not reached 0...

Page 43: ...y fan 8 2 Maintenance frequency Carry out a regular inspection according to the following recommendations Body When commissioned At least every 6 months Turbine Check the direction of rotation check t...

Page 44: ...4 Electric fan replacement 8 4 1 JBRB ECOWATT PR 04 to 22 Shut off the power supply Unscrew the 2 door screws then remove the door Disconnect the on off switch power cable Unfasten the 4 latches then...

Page 45: ...e set fan wheel rotates freely and that no objects are liable to be launched by the turbine Replace the cover and fasten the latches Reconnect the power supply and replace the door 8 4 2 JBRB ECOWATT...

Page 46: ...JBRB ECOWATT 38 Three phase 157113 Controller 1 COMPACTO 08 Controller for JBRB ECOWATT 48 Single phase 1571161002 Controller 1 INVENTO S15 Controller for JBRB ECOWATT 48 Three phase 157114 Controller...

Page 47: ...47 48 NT00000603 JBRB ECOWATT PR AN 191202...

Page 48: ...ntinuously improving equipment the manufacturer reserves the right to make any technical modifications without giving prior notice VIM Les pr s de M gy Sud SOUDAN CS 60120 79401 ST MAIXENT L ECOLE CED...