ViM BATE-R010 Instruction Manual Download Page 8

 

8/8 

NT00000592-BATE-R-010-AN-191114

Cut off the power supply before opening the unit, 

Do not touch live parts: Danger of death!

The printed circuit board is electrically charged when the heating device is live,

Indications of green “MODE” and red diodes

:

The diode 

 above is on when the heater is heating,

The green MODE diode flashes once every 5 seconds (for 1 minute), then once a second,

5.2  Fault resolution 

If the green MODE diode stays on, there is an air volume sensor fault,

If there is no air flow, the green MODE diode flashes once every 5 seconds,

Work must be carried out before operating the heater again,

If there is no air flow, the green MODE diode flashes once every 5 seconds, When the air flow resumes, 

the heater starts up again in normal mode,

If the manual reset safety thermostat is activated, 
take the following measures:

Cut off the power supply,

Carefully identify why the safety thermostat was ac-
tivated,
Once the error has been corrected, press the man-
ual safety thermostat “reset” button on the electrical 
heater cover.

5.3  Maintenance

Regular inspection of connections,
Disassemble and clean the electrical heater as often as required by regulations and at least once a year,

6. 

WASTE MANAGEMENT

6.1  Treatment of packaging and General Industrial Waste (GIW)

The packaging (pallets not on deposit, cartons, films, wooden boxes) and other GIW must be made reus

-

able by an approved service provider,
It is strictly prohibited to burn, bury or dump them in the natural environment,

6.2  Treatment of Professional WEEE

This product must not be dumped or treated with household refuse, but must be dropped off at an appro

-

priate collection point for waste electrical and electronic equipment (WEEE), 

Non-binding document. With a view to continuously improving equipment, the manufacturer reserves the 

right to make any technical modifications without giving prior notice.

VIM
Les prés de Mégy Sud – SOUDAN - CS 60120 - 79401 ST MAIXENT L’ECOLE CEDEX
Tel.: 05 49 06 60 38 or 05 49 06 60 25 – Fax: 05 49 06 60 36
[email protected] - www.vim.fr

Summary of Contents for BATE-R010

Page 1: ...NSTRUCTION MANUAL INSTALLATION WIRING COMMISSIONING MAINTENANCE AFNOR CERTIFICATION ISO 14001 Environnement AFNOR CERTIFICATION ISO 9001 Q u a l i t BATE R010 Circular electrical heater with built in...

Page 2: ...instructions carefully as they contain important infor mation for your safety and user safety during installation operation and maintenance of this product Once installation is complete ensure this ma...

Page 3: ...ent is covered by a 12 month warranty Only parts from the date of invoice The seller undertakes to replace all parts or equipment that we recognise as malfunctioning to the exclu sion of any damages o...

Page 4: ...0 2 850 BATE R010 400 3 000W Single phase 3 000 13 0 9 1 276 376 470 50 0 680 4 600 BATE R010 400 5 000W Single phase 5 000 21 7 10 2 276 376 470 50 0 680 4 600 400V Three phase power supply BATE R010...

Page 5: ...equipped with two safety thermostats to avoid overheating An automatic reset safety thermostat 50 C and a manual reset safety thermostat 100 C located on the cover They must control an external contac...

Page 6: ...5 10 0 10VDC N L 230V 50Hz 4kW Equipment Included Optional BATE R010 Electrical heater MCR1 Post ventilation delay 4 3 BATE R010 Three phase Power 18kW 3 phases power supply airflow controller auto re...

Page 7: ...f the fan without the heater shutting off beforehand MCR1 type post ventilation delay if necessary or at the same time to be avoided Post ventilation block diagram BDEZ Safety thermostats fitted withi...

Page 8: ...tivated Once the error has been corrected press the man ual safety thermostat reset button on the electrical heater cover 5 3 Maintenance Regular inspection of connections Disassemble and clean the e...