1.2  Safety instructions 

Put on appropriate PPE (Personal Protective Equipment) before any work,

If work has to be carried out on the device, cut off the power supply on the main circuit breaker and make 

sure that nobody can accidentally turn it back on,

Before operating the equipment, check the following points:

•  Make sure that the device does not contain any foreign bodies, 
•  Check that all the components are mounted in their original positions,
•  Check the earth connection, 
•  Check that the access hatch is properly closed,

1.3  Reception - Storage

In case of short shipment, non-conformity, and/or total or partial damage to the products delivered, the 
Buyer must, in accordance with article 133-3 of the French Commercial Code, add written reservations to 

the carrier’s delivery slip and confirm them within 72 hours by registered letter with acknowledgement of 

receipt with a duplicate for the seller, If the equipment is received without express reservation, the Buyer 
has no subsequent recourse against us, 
The product must be stored protected from weather, shocks and soiling due to splashing of any kind during 

its transport from the supplier to the final customer and on the site before installation,

1.4  Warranty 

The equipment is covered by a 12-month warranty - Only parts - from the date of invoice, 
The seller undertakes to replace all parts or equipment that we recognise as malfunctioning, to the exclu-
sion of any damages or penalties such as operating losses, market injury or other non-material or indirect 
damage,
The following are excluded from our warranty: faults connected with abnormal use or use not in accord-
ance with the recommendations in our manuals and instructions, defects found following normal wear and 
tear, incidents caused by negligence, failure to monitor or maintain correctly, defects due to poor installa-
tion of the equipment or to poor storage conditions before installation,

In any event, the seller is not responsible for equipment that has been modified or repaired even partially,

2. 

RANGE / PRODUCT PRESENTATION

•  Diameters from 125 to 500mm,
•  Power from 600 to 18 000W 
•  Single-phase 230V 50Hz or three-phase 400V 50Hz power supply,

Standard construction

•  Circular shell and Aluzinc treated steel IP44 connection box,
•  Connection with class-C waterproof joints,
•  IP44 cable grommet for cutting
•  Sheathed 304 stainless steel heating elements,
•  1 automatic reset safety thermostat, set to 50°C,
•  1 manual reset safety thermostat, set to 100°C,
•  2 heating (red) / operating mode-fault (green) indicator LEDs
•  1 Triac-type electronic power regulator controlled by an external 0 - 10V signal,
• 

1 air volume cut-out sensor, which shuts off the heating if the air speed is below 1,5m/s,

Summary of Contents for BATE-R010

Page 1: ...NSTRUCTION MANUAL INSTALLATION WIRING COMMISSIONING MAINTENANCE AFNOR CERTIFICATION ISO 14001 Environnement AFNOR CERTIFICATION ISO 9001 Q u a l i t BATE R010 Circular electrical heater with built in...

Page 2: ...instructions carefully as they contain important infor mation for your safety and user safety during installation operation and maintenance of this product Once installation is complete ensure this ma...

Page 3: ...ent is covered by a 12 month warranty Only parts from the date of invoice The seller undertakes to replace all parts or equipment that we recognise as malfunctioning to the exclu sion of any damages o...

Page 4: ...0 2 850 BATE R010 400 3 000W Single phase 3 000 13 0 9 1 276 376 470 50 0 680 4 600 BATE R010 400 5 000W Single phase 5 000 21 7 10 2 276 376 470 50 0 680 4 600 400V Three phase power supply BATE R010...

Page 5: ...equipped with two safety thermostats to avoid overheating An automatic reset safety thermostat 50 C and a manual reset safety thermostat 100 C located on the cover They must control an external contac...

Page 6: ...5 10 0 10VDC N L 230V 50Hz 4kW Equipment Included Optional BATE R010 Electrical heater MCR1 Post ventilation delay 4 3 BATE R010 Three phase Power 18kW 3 phases power supply airflow controller auto re...

Page 7: ...f the fan without the heater shutting off beforehand MCR1 type post ventilation delay if necessary or at the same time to be avoided Post ventilation block diagram BDEZ Safety thermostats fitted withi...

Page 8: ...tivated Once the error has been corrected press the man ual safety thermostat reset button on the electrical heater cover 5 3 Maintenance Regular inspection of connections Disassemble and clean the e...

Reviews: