TECHNICAL DATA

September 17, 2009

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

MODEL VKFD25U

PRE-ASSEMBLED FLEXIBLE 

SPRINKLER DROP

ASSEMBLIES 

(UNBRAIDED)  

DESIGN CRITERIA

cULus Listing Requirements: 

 

• Approved for use in ceilings with medium and heavy load grids (ASTM C635 and C636).

• Compatible with Viking CPVC BlazeMaster

®

 sprinkler systems.

• Meets NFPA 13, NFPA 13D and NFPA 13R guidelines and EN12845.

• Intended for use in wet or dry systems.

• The maximum permissible number of bends is (2) x 90° for 39-3/8“ lengths at the manufacturer’s specified bend radius of 4” (102 mm) for 

cULus.

• In suspended ceiling, Viking Flexible Sprinkler Drops must be installed in accordance with Viking Flex Drop Installation and Design Manual, Form

No. F_112107.

• In suspended ceilings, outlet reducer must be secured to the ceiling support system with brackets supplied.

Hydraulic calculations for NFPA systems must include the values in Table 3 on page 138j using the maximum number of bends that includes 

the inlet and outlet fittings as indicated. Authorities Having Jurisdiction will require proper hydraulic calculations and inspect for proper 
bend radii and maximum quantity of bends as indicated in the table. Refer to the Viking Flex Drop Installation and Design Manual, Form No. 
F_112107, for proper application and installation of Flexible Sprinkler Drops.

NOTE: Refer to the specific sprinkler data page for the sprinkler model used with the Flexible Sprinkler Drop.

CAUTIONS:

• 

Minimum Inside Bend Radius: 4” (102 mm) Static cULus unbraided

• Maximum Sprinkler K-Factor: 5.6 U.S. (80.6 metric)

• Maximum Number of Bends per Hose: Refer to Table 3 on page 138j.

•  Repeated bending of one portion of the flexible tube before installation may cause breakage or loss of resisting pressure.

•  When using concealed sprinklers, they must be installed in neutral or negative pressure plenums only.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to the 

appropriate sprinkler data page. Viking sprinklers and Flexible Sprinkler Drops are designed to be installed 
in accordance with the latest edition of Viking technical data, the latest standards of NFPA, FM Global, LPCB, 
APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, 
and standards whenever applicable. The use of certain types of sprinklers may be limited due to occupancy and 
hazard. Refer to the Authority Having Jurisdiction prior to installation.

Form No. F_091509

Sprinkler 138l

New page 138g-l, issued September 17, 2009. 

Summary of Contents for VKFD25U

Page 1: ...klers the mounting bracket system and special outlet fit tings provide a generous amount of adjustment both laterally and vertically for flush and precise sprinkler installation Note The brackets must be attached to the ceiling s main tee bar supports not to the cross support rail members The unique assembly of the Viking Flexible Sprinkler Drop to the piping system and the outlet sprinkler fittin...

Page 2: ...port bracket bracket square nut and wing bolt assembled over straight outlet fitting sprinklers see Table 1 installed and leak tested into the outlet fitting as speci fied 10 per kit Instructions 1 For frame style sprinkler VK302 add the sprinkler Finish and Temperature Rating Suffix to the Sprinkler Base Part No A For Chrome sprinkler rated 135 F 57 C Add the suffix FA For White sprinkler rated 1...

Page 3: ...rder Separately Optional 4 Bend Radius Gauge Tool Part No 15450 plastic Optional 4 Fixed Radius Clip Part No 14403 plastic The Following Kits are Available for Replacement Components Note These kits may be ordered in addition to the above for replacing components as required A 49 3 16 1 250 mm long support bar is available when the main support beams are spaced at 4 ft 1 219 mm These must be order...

Page 4: ...tandards Deviations from these standards or any alterations to the sup port system or sprinkler after leaving the factory including but not limited to painting plating coating or modification may render the sprinkler inoperative or the support system non compliant automatically nullifying the approvals and any guarantee made by The Viking Corporation The use of certain types of sprinklers may be l...

Page 5: ...inspection requirements that must be followed A Sprinklers must be inspected on a regular basis for corrosion mechanical damage obstructions paint etc The frequency of inspections may vary due to corrosive atmospheres water supplies and activity around the device B Sprinklers that have been field painted or mechanically damaged must be replaced immediately Sprinklers showing signs of corrosion sha...

Page 6: ...nspect for proper bend radii and maximum quantity of bends as indicated in the table Refer to the Viking Flex Drop Installation and Design Manual Form No F_112107 for proper application and installation of Flexible Sprinkler Drops NOTE Refer to the specific sprinkler data page for the sprinkler model used with the Flexible Sprinkler Drop CAUTIONS Minimum Inside Bend Radius 4 102 mm Static cULus un...