TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

SPRINKLER OVERVIEW

Page 2 of 3

Form No. F_080814       18.12.06       Rev 14.1.P65

VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a 

water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow 

arrow in the direction of discharge. Marked “SIDEWALL” on the deflector with an arrow and the word “FLOW”. (Note: Some 

vertical sidewall sprinklers can only be installed in the upright or pendent position—in this case, the sprinkler will also be marked 

“UPRIGHT” or “PENDENT”.)

HORIZONTAL SIDEWALL (HSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The special deflector 

provides a water spray pattern outward in a quarter-spherical pattern. Most of the water is directed away from the nearby wall 

with a small portion directed at the wall behind the sprinkler. The top of the deflector is oriented parallel with the ceiling or roof. 

The flow arrows point in the direction of discharge. Marked “SIDEWALL” and “TOP” with an arrow and the word “FLOW”.

EXTENDED COVERAGE (EC) SPRINKLER: A spray sprinkler designed to discharge water over an area having the maximum 

dimensions indicated in the individual listings. Maximum area of coverage, minimum flow rate, orifice size, and nominal K-Factor 

are specified in the individual listings. EC sprinklers are intended for Light-Hazard occupancies with smooth, flat, horizontal ceil-

ings unless otherwise specified. In addition to the above markings, the sprinkler is marked “EC”.

QUICK RESPONSE (QR) SPRINKLER: A spray sprinkler with a fast- actuating operating element. The use of quick response 

sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction (AHJ) prior to installing.

QUICK RESPONSE EXTENDED COVERAGE (QREC) SPRINKLER: A spray sprinkler designed to discharge water over an area 

having the maximum dimensions indicated in the individual listing. This is a sprinkler with an operating element that meets the 

criteria for quick response. QREC sprinklers are only intended for Light Hazard occupancies. The sprinkler is marked “QREC”.

FLUSH SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The unit is mounted 

flush with the ceiling or wall, with the fusible link exposed. Upon actuation, the deflector extends beyond the ceiling or wall to 

distribute water discharge. The sprinkler is marked “SSP”, “PEND”, or “SIDEWALL” and “TOP”.

CONCEALED SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The sprinkler is 

hidden from view by a cover plate installed flush with the ceiling or wall. During fire conditions, the cover plate detaches, and 

upon sprinkler actuation, the deflector extends beyond the ceiling or wall to distribute water discharge. The sprinkler is marked 

“SSP”, “PEND”, or “SIDEWALL” and “TOP”.  

RECESSED SPRINKLER: A spray sprinkler assembly intended for installation with a concealed piping system. The assembly con-

sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond 

the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity. Refer to the appropriate technical data page 

for allowable sprinkler models, temperature ratings, and occupancy classifications. DO NOT RECESS ANY SPRINKLER NOT 

LISTED FOR USE WITH THE ESCUTCHEON.

CORROSION-RESISTANT SPRINKLER: A special service sprinkler with non-corrosive protective coatings, or that is fabricated 

from non-corrosive material, for use in atmospheres that would normally corrode sprinklers.

DRY SPRINKLER: A special-service sprinkler intended for installation on dry pipe systems or wet pipe systems where the sprinkler 

is subject to freezing temperatures. The unit consists of a sprinkler permanently secured to an extension nipple with a sealed 

inlet end to prevent water from entering the nipple until the sprinkler operates. The unit MUST be installed in a tee fitting. Dry 

upright sprinklers are marked with the “B” dimension [distance from the face of the fitting (tee) to the top of the deflector]. Dry 

pendent and sidewall sprinklers are marked with the “A” dimension [the distance from the face of fitting (tee) to the finished 

surface of the ceiling or wall].

LARGE DROP SPRINKLER: A type of special application sprinkler used to provide fire control of specific high-challenge fire haz-

ards. Large drop sprinklers are designed to produce an umbrella-shaped spray pattern downward with a higher percentage of 

“large” water droplets than standard spray sprinklers. The sprinkler has an extra-large orifice with a nominal K-Factor of 11.2. 

Marked “HIGH CHALLENGE” and “UPRIGHT”.

EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER: A sprinkler intended to provide fire suppression of specific high-

challenge fire hazards through the use of a fast response fusible link, 14.0, 16.8, or 25.2 nominal K-Factor, and special deflector. 

ESFR sprinklers are designed to produce high-momentum water droplets in a hemispherical pattern below the deflector. This 

permits penetration of the fire plume and direct wetting of the burning fuel surface while cooling the atmosphere early in the 

development of a high-challenge fire. Marked “ESFR” and “UPRIGHT” or “PEND”.

INTERMEDIATE LEVEL/RACK STORAGE SPRINKLER: A standard spray sprinkler assembly designed to protect its operating 

element from the spray of sprinklers installed at higher elevations. The assembly consists of a standard or large orifice upright 

or pendent sprinkler with an integral upright or pendent water shield and guard assembly. Use only those sprinklers that have 

been tested and listed for use with the assembly. Refer to the technical data page for allowable sprinkler models.

RESIDENTIAL SPRINKLER: A sprinkler intended for use in the following occupancies: one- and two-family dwellings with the fire 

protection sprinkler system installed in accordance with NFPA 13D; residential occupancies up to four stories in height with the 

fire protection system installed in accordance with NFPA 13R; and where allowed by the Authority Having Jurisdiction in resi-

dential portions of any occupancy with the fire protection system installed in accordance with NFPA 13.

Summary of Contents for VK950

Page 1: ...and 10 as well as obstructed wood truss construction see Figure 11 When using steel pipe COIN Sprinklers can be applied as a dry system using air or gas as a supervisory medium see Figures 7 11 In certain scenarios draft curtains are NOT required when sprinkler spacing meets either of the following criteria also refer to Design Criteria 14 X 14 4 3 m X 4 3 m for solid wood joists or trusses on edg...

Page 2: ... Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Screw Brass UNS C36000 Pip Cap and Insert Assembly Copper UNS C11000 and Stainless Steel UNS S30400 Ordering Information Refer to Table 1 4 INSTALLATION Refer to appropriate NFPA Installation Standards 5 OPERATION During a fire condition the heat sensitive liquid in the glass bulb expands causing the glass to shatter releasi...

Page 3: ...red Temperature Rating Sprinkler Base Part No Size 1 Finishes 2 Temperature Ratings4 Classification Intermediate NPT Inch Description Suffix Nominal Rating Bulb Color Max Ambient Ceiling Temperature1 Suffix 20757 1 2 Brass A 200 F 93 C Green 150 F 65 C E ENT 2 3 JN Corrosion Resistant Coating ENT2 3 Example 20757AE VK950 with Brass Finish and 200 F 93 C Nominal temperature rating This sprinkler is...

Page 4: ...ction The draft curtain must be constructed of material that will not allow heat to escape through or above it this may be 6 mm thick plywood Draft curtains are NOT required when sprinkler spacing is up to 14 X 14 4 3 m X 4 3 m for solid wood joists or trusses on edge see Figure 13B Draft curtains are NOT required when sprinkler spacing is up to 16 X 16 4 9 m X 4 9 m for truss construction on face...

Page 5: ...n or 1 3 the depth of the space measured from the top surface of the ceiling to the bottom of the deck above The CPVC pipe can supply the COIN Sprinklers and the ceiling sprinklers below Use all guidelines and installation instructions as specified by the CPVC pipe manufacturers unless specified differently in this data sheet When using 1 DN25 pipe or larger a hanger must be located at the truss n...

Page 6: ...ervices 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 4 Open Wood Truss and Open Web Steel Joist Construction with Non Combustible Insulation Filling to Bottom of the Top Cord Using CPVC Pipe Cross Section View Figure 3 Open Wood Truss and Open Web Steel Joist Construction Using ...

Page 7: ...Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 5 Solid Wood or Composite Wood Joist Construction with Non Combustible Insulation Filling Upper Deck Using CPVC Pipe Cross Section View Figure 6 CPVC Piping Installed as a Vertical Riser ...

Page 8: ... space for open wood truss construction to 2000 ft2 185 m2 with their top chord members on face not on edge and 2000 ft2 185 m2 for solid wood joists Insulated top chord spaces on edge confine heat localized detection area to 2000 ft2 185 m2 non insulated top chord spaces on edge confine heat localized area to 1 000 ft2 93 m2 The draft curtain may be constructed of 6 mm thick plywood to prevent he...

Page 9: ...omposite wood joists is 1000 ft2 93 m2 For dry pipe systems 1 The remote area for open wood truss construction or open bar joist construction with the top chord members on face not on edge is 1000 ft2 93 m2 or 6 sprinklers whichever is greater See Table 2 Draft curtains are NOT required when sprinkler spacing is up to 16 X 16 4 9 m X 4 9 m The remote area for this application is the same as above ...

Page 10: ...01 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 8 Solid Wood or Composite Wood Joist Construction with Non Combustible Insulation Filled Upper Deck Steel Pipe Cross Sectional View Figure 9 Unobstructed Open Wood Truss and Open Steel Bar Joist Steel Pipe Cross ...

Page 11: ...echnical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 11 Obstructed Wood Truss Construction Steel Pipe Cross Sectional View Figure 10 Open Wood Truss and Open Web Steel Joist Construction with Non Combustible Insulation Filling to Bottom of the Top Cord Using Steel Pipe...

Page 12: ...stings MI 49058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 12 Wood Truss Construction with Chords on Face and Non combustible Insulation Provided to the Bottom of the Trusses CPVC and Steel Pipe Cross Section View ...

Page 13: ... Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Visit the Viking website for the latest edition of this technical data page www vikinggroupinc com Figure 13A Trusses on Face Figure 13B Trusses on Edge 1 1 2 38 mm 1 1 2 38 mm On Edge On Face Example of Typical 2x4 Construction Refer to Design Critera Example of Typical 2x4 Construction Refer to Design Critera 3 1 2 8...

Page 14: ...om of Obstruction Y 1 0 300 mm 0 0 mm 1 0 to 1 6 300 mm to 450 mm 0 0 mm 1 6 to 2 0 450 mm to 600 mm 1 25 mm 2 0 to 2 6 600 mm to 750 mm 1 25 mm 2 6 to 3 0 750 mm to 900 mm 1 75 mm 3 0 to 3 6 900 mm to 1 1 m 3 75 mm 3 6 to 4 0 1 1 m to 1 2 m 3 75 mm 4 0 to 4 6 1 2 m to 1 4 m 5 125 mm 4 6 to 5 0 1 4 m to 1 5 m 7 175 mm Distance from Sprinkler to Side of Obstruction X Maximum Allowable Distance of D...

Page 15: ... the sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may af...

Page 16: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Page 17: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Page 18: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Page 19: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Page 20: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Page 21: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Page 22: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Page 23: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Page 24: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Page 25: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Page 26: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Reviews: