Service Procedure
©2007 Viking Preferred Service
35
Comparison of CFC12 and HFC134a Properties
Properties/Characteristics CFC12
HFC134a
Ozone Depletion Potential (ODP)
1.0*
0.0*
Global Warming Potential (GPW)
3.2*
0.27*
Molecular weight
121
102
Boiling point at 1 atmosphere
-22°F
(-30°C)
-15°F
(-126°C)
Vapor pressure at 77°F (25°C)
80 psig
82 psig
Liquid density at 77°F (25°C)
82 lb/ft
3
75
lb/ft
3
Flammability No
No
High-side system operating
Pressure at 65°F (18°C)
HFC134a approximately
3 psig higher than CFC12
Low-side system operating
Pressure at 65°F (18°C)
HFC134a approximately
2 psig lower than CFC12
CAUTION
To minimize contamination, exercise extreme care
when servicing HFC134A sealed systems.
•
No trace of other refrigerants is allowed in HFC134a
systems. Chlorinated molecules in other refrigerants
such as CFC12, etc. will lead to capillary tube
plugging.
•
Ester oil is used in HFC134a systems. Do not use
mineral oil. HFC134a and mineral oils cannot be
mixed. If mineral oils were used in HFC134a
systems, lubricant would not return to compressor
and would cause early compressor failure. If
significant amount of oil has been lost from
compressor, replace oil rather than adding oil.
•
Ester oils used in HFC134a systems are so
hydroscopic that by the time an inadequate system
performance is detected, oil will be saturated with
moisture.
•
CFC12 has much higher tolerance to system
processing materials, such as drawing compounds,
rust inhibitors, and cleaning compounds, than
HFC134a. Such materials are not soluble in
HFC134a systems. If materials were to be washed
from system surfaces by ester oils, they could
accumulate and eventually plug capillary tube.
•
Care must be taken to minimize moisture entering
HFC134a system. Do not leave compressor or
system open to atmosphere for more than 10
minutes. Excessive moisture in HFC134a system
will react with compressor oil and generate acid.
•
Compressor must be replaced when performing low
side leak repair.
•
Drier filter must always be replaced with service
drier filter.
IMPORTANT:
Unbrazing drier filter from tubing will
drive moisture from desiccant and into
system, causing acids to form. Do not
unbraze filter drier from tubing. If CFC12
service drier was installed in HFC134A
system, drier could overload due to
excessive moisture.
•
HFC134a compatible copper tubing must be used
when replacing tubing.
•
Avoid system contamination when flaring, swagging,
or cutting refrigeration tubing.
Brazing
CAUTION
To avoid risk of personal injury or property damage,
take necessary precautions against high
temperatures required for brazing.
Satisfactory results require cleanliness, experience, and
use of proper materials and equipment.
Connections to be brazed must be properly sized, free of
rough edges, and clean.
Generally accepted brazing materials are:
•
Copper to copper joints:
SIL-FOS (alloy of 15 percent silver, 80 percent
copper, and 5 percent phosphorous). Use without
flux. Recommended brazing temperature is
approximately 1400°F. Do not use for copper to
steel connection.
•
Copper to steel joints:
SILVER SOLDER (alloy of 30 percent silver, 38
percent copper, 32 percent zinc). Use with fluoride
based flux. Recommended brazing temperature is
approximately 1200°F.
•
Steel to steel joints:
SILVER SOLDER (see copper to steel joints).
•
Brass to copper joints:
SILVER SOLDER (see copper to steel joints).
•
Brass to steel joints:
SILVER SOLDER (see copper to steel joints).
Summary of Contents for DDBF036LSS
Page 18: ......
Page 50: ...Appendix A 50 2007 Viking Preferred Service NOTES ...