VK3522 QUICK RESPONSE 

PENDENT SPRINKLER (K8.0)

TECHNICAL DATA

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Page 6 of 6

Form No. F_021416     Rev 22.1     March 3, 2022

Models E-1 or NP-1

Recessed Escutcheon

Ceiling opening size:

Minimum: 2-5/16” (59 mm)

Maximum: 2-1/2” (64 mm) 

2-1/8” (54 mm)

2-1/8” (54 mm)

Models E-2, E-3, NP-2 or

NP-3 Thread-On Recessed

Escutcheon

(E-3 and NP-3 Outer rings

have larger diameters)

Max. 1-7/16” 

(37 mm)

Max. 1-3/4” 

(44 mm)

Min. 13/16” 

(21 mm)

Min. 15/16” 

(24 mm)

Ceiling opening size:

Minimum: 2-5/16” (59 mm)

Maximum: 2-1/2” (64 mm) 

1-7/16” 

(37 mm)

Standard Surface-Mounted Escutcheon

Figure 6: Installation Dimensions with Viking Escutcheons

1. Install the escutcheon onto the 

sprinkler threads. 

Figure 5: Installation (with Straight Wrench)

2. Carefully slide the wrench** sideways 

around the protective cap then push 

upwards to engage with the sprinkler 

wrench flats.

3. Install the sprinkler and escutcheon 

assembly into the pipe fitting. Be sure 

the escutcheon contacts the surface 

of the finished ceiling. 

Replaces Form No. F_021416 Rev 21.3

(Added LPCB and VdS details)

Summary of Contents for 23874

Page 1: ...5 bar Rated to 175 psi 12 bar water working pressure Factory tested hydrostatically to 500 psi 34 5 bar Thread size 1 2 NPT 15 mm BSPT Nominal K factor 8 0 U S 115 metric Glass bulb fluid temperature...

Page 2: ...ature rated sprinkler Accessories Sprinkler Wrenches see Figure 1 A Installer Wrench Part No 22055 available since 2017 B Cabinet Wrench Part No 20901M B available since 2017 C Recessed Socket Wrench...

Page 3: ...55 F 68 C 175 F 79 C and 200 F 93 C C 155 F 68 C 175 F 79 C 200 F 93 C and 286 F 141 C D 155 F 68 C 175 F 79 C and 200 F 93 C Approved Finishes 1 Brass Chrome White Polyester 3 4 Black Polyester 3 4 a...

Page 4: ...applicable DESIGN CRITERIA FM FM Approval Requirements The Viking VK3522 Quick Response Pendent Sprinkler is FM Approved as quick response Non Storage Pendent sprinkler as indicated in the FM Approval...

Page 5: ...3 Recessed Installation with Recessed Socket Wrench A 1 2 ratchet is required not available from Viking Figure 4 Recessed Installation with standard Installer s Wrench 2 Carefully slide the wrench sid...

Page 6: ...3 Thread On Recessed Escutcheon E 3 and NP 3 Outer rings have larger diameters Max 1 7 16 37 mm Max 1 3 4 44 mm Min 13 16 21 mm Min 15 16 24 mm Ceiling opening size Minimum 2 5 16 59 mm Maximum 2 1 2...

Page 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Page 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Page 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Page 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Page 11: ...readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification...

Page 12: ...y intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler...

Page 13: ...ENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking C...

Page 14: ...e sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any s...

Page 15: ...ctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements...

Page 16: ...her To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVI...

Page 17: ...rior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service d...

Page 18: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Page 19: ...render the sprinkler inoperative and will automatically nullify the approval and any guarantee made by The Viking Corporation Refer to the Authority Having Jurisdiction prior to installation 2 GENERA...