STANDARD/QUICK RESPONSE 

EXTENDED COVERAGE 

UPRIGHT SPRINKLER 

VK532 (K11.2)

TECHNICAL DATA

Page 6 of 6

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Form No. F_053114   19.10.14     Rev 19.1

Approval Chart 2 (FM)

Quick Response Extended Coverage ELO Upright Sprinkler VK532

For HC-1, HC-2, and HC-3 Occupancies

Maximum 175 PSI (12 Bar) WWP

Maximum Sprinkler

 

Spacing (L x W

2

)

Maximum Area

 

per Sprinkler

Refer to Design Criteria below.

NOTE: FM installation guidelines may differ 

from cULus and/or NFPA criteria. Refer to the 

latest applicable FM Loss Prevention 

Data Sheets (including 2-0 and 3-26).

FM Approval

Upright Sprinkler VK532

16 ft. x 16 ft. (4.9 m x 4.9 m)

256 ft

2

 (23.8 m

2

)

A1

18 ft. x 18 ft. (5.5 m x 5.5 m)

324 ft

2

 (30.1 m

2

)

A1

20 ft. x 20 ft. (6.1 m x 6.1 m)

400 ft

2

 (37.2 m

2

)

A1

Approved Temperature Ratings

A - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)

Approved Finishes

1 - Brass, Chrome, White Polyester, Black Polyester, ENT

3

Footnotes

1

 This chart shows the FM Approvals available at time of printing. Check with the manufacturer for any additional approvals.

2

 To determine “Minimum Water Supply Requirement” for areas of coverage where length and width of actual sprinkler spacing are not equal, select the “Maximum Sprinkler 

Spacing” from the chart that is equal to or greater than the larger of the actual spacing (length or width) dimensions used. Example: When using 10’-6” x 13’-0” sprinkler spacing, 

provide the “Minimum Water Supply Requirement” listed in the chart for 14’-0” x 14’-0” spacing. For areas of coverage smaller than shown, use the “Minimum Water Supply 

Requirement” in the appropriate hazard group for the next larger area listed. The distance from sprinklers to walls shall not exceed one-half the “Maximum Sprinkler Spacing” 

listed for the “Minimum Water Supply Requirement” used.

3

 FM Approved as corrosion resistant.

DESIGN CRITERIA - FM 

(Also refer to Approval Chart 2 above.)

FM Approval Requirements:

 

Sprinkler VK532 is FM Approved as a quick response 

Non-Storage

 extended coverage upright sprinkler as indicated in the FM Approval Guide for 

use in occupancy hazard classifications HC-1, HC-2, and HC-3. For specific application and installation requirements, reference the latest applicable 

FM Loss Prevention Data Sheets (including Data Sheets 2-0 and 3-26). FM Global Loss Prevention Data Sheets contain guidelines relating to, but 

not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and 

deflector distance below the ceiling.

NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614

 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza

-

tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. 

Replaces Form No. F_053114 Rev 18.2.P65

(Added ENT; updated FM language.)

  

Summary of Contents for 08687

Page 1: ...4 5 bar Factory tested hydrostatically to 500 psi 34 5 bar Thread size 3 4 20 mm NPT Nominal K Factor 11 2 U S 161 3 metric Metric K factor measurement shown is in Bar When pressure is measured in kPa...

Page 2: ...bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern...

Page 3: ...rinkler Finishes Brass Chrome White Polyester3 Black Polyester3 and ENT Corrosion Resistant Coatings4 ENT Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Ot...

Page 4: ...min 84 Bar D1 D2 16 ft x 16 ft 4 9 m x 4 9 m 256 ft2 23 8 m2 30 gpm 7 2 psi 113 6 L min 50 Bar B1 E2 18 ft x 18 ft 5 5 m x 5 5 m 324 ft2 30 1 m2 33 gpm 8 7 psi 124 9 L min 60 Bar B1 E2 20 ft x 20 ft...

Page 5: ...ly cULus Listed for Ordinary Hazard Occupancies For non combustible obstructed construction within trusses or bar joists having non combustible web members greater than 1 25 4 mm when applying the 4 t...

Page 6: ...When using 10 6 x 13 0 sprinkler spacing provide the Minimum Water Supply Requirement listed in the chart for 14 0 x 14 0 spacing For areas of coverage smaller than shown use the Minimum Water Supply...

Page 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Page 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Page 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Page 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Page 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Reviews: