STANDARD/QUICK RESPONSE
EXTENDED COVERAGE
UPRIGHT SPRINKLER
VK532 (K11.2)
TECHNICAL DATA
Page 6 of 6
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com
Form No. F_053114 19.10.14 Rev 19.1
Approval Chart 2 (FM)
Quick Response Extended Coverage ELO Upright Sprinkler VK532
For HC-1, HC-2, and HC-3 Occupancies
Maximum 175 PSI (12 Bar) WWP
Maximum Sprinkler
Spacing (L x W
2
)
Maximum Area
per Sprinkler
Refer to Design Criteria below.
NOTE: FM installation guidelines may differ
from cULus and/or NFPA criteria. Refer to the
latest applicable FM Loss Prevention
Data Sheets (including 2-0 and 3-26).
FM Approval
1
Upright Sprinkler VK532
16 ft. x 16 ft. (4.9 m x 4.9 m)
256 ft
2
(23.8 m
2
)
A1
18 ft. x 18 ft. (5.5 m x 5.5 m)
324 ft
2
(30.1 m
2
)
A1
20 ft. x 20 ft. (6.1 m x 6.1 m)
400 ft
2
(37.2 m
2
)
A1
Approved Temperature Ratings
A - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)
Approved Finishes
1 - Brass, Chrome, White Polyester, Black Polyester, ENT
3
Footnotes
1
This chart shows the FM Approvals available at time of printing. Check with the manufacturer for any additional approvals.
2
To determine “Minimum Water Supply Requirement” for areas of coverage where length and width of actual sprinkler spacing are not equal, select the “Maximum Sprinkler
Spacing” from the chart that is equal to or greater than the larger of the actual spacing (length or width) dimensions used. Example: When using 10’-6” x 13’-0” sprinkler spacing,
provide the “Minimum Water Supply Requirement” listed in the chart for 14’-0” x 14’-0” spacing. For areas of coverage smaller than shown, use the “Minimum Water Supply
Requirement” in the appropriate hazard group for the next larger area listed. The distance from sprinklers to walls shall not exceed one-half the “Maximum Sprinkler Spacing”
listed for the “Minimum Water Supply Requirement” used.
3
FM Approved as corrosion resistant.
DESIGN CRITERIA - FM
(Also refer to Approval Chart 2 above.)
FM Approval Requirements:
Sprinkler VK532 is FM Approved as a quick response
Non-Storage
extended coverage upright sprinkler as indicated in the FM Approval Guide for
use in occupancy hazard classifications HC-1, HC-2, and HC-3. For specific application and installation requirements, reference the latest applicable
FM Loss Prevention Data Sheets (including Data Sheets 2-0 and 3-26). FM Global Loss Prevention Data Sheets contain guidelines relating to, but
not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and
deflector distance below the ceiling.
NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.
IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614
for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest
edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza
-
tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable.
Replaces Form No. F_053114 Rev 18.2.P65
(Added ENT; updated FM language.)