TECHNICAL DATA

Page 5 of 6

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Form No. F_053114   19.10.14     Rev 19.1

DESIGN CRITERIA - UL 

(Also refer to Approval Chart 1.)

cULus Listing Requirements:

EC-ELO Upright Sprinkler VK532 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for 

extended coverage upright sprinklers as indicated below:

• 

The minimum water supplies and maximum areas of coverage shown in Approval Chart 1 are designed to provide the following design densities: 

0.10 gpm/ft

2

 (4.1 mm/min) for Light Hazard densities; 0.15 gpm/ft

2

 (6.1 mm/min) for Ordinary-Hazard Group I densities; 0.2 gpm/ft.

2

 (8.1 mm/min) 

for Ordinary-Hazard Group II densities.

• 

The sprinkler installation rules contained in NFPA 13 for extended coverage upright spray sprinklers must be followed.

• 

Viking EC-ELO Upright Sprinklers are cULus Listed for use in unobstructed construction, and noncombustible obstructed construction consisting 

of solid steel and/or concrete beams as defined in the latest edition of NFPA 13.

• 

Ceiling slope not to exceed 2/12 (9.5°).

Als

o, 

Viking ECOH-ELO Upright Sprinkler VK532 is specifically cULus Listed for Ordinary Hazard Occupancie

s:

• 

For non-combustible obstructed construction within trusses or bar joists having non-combustible web members greater than 1” (25.4 mm) when 

applying the 4 times obstruction criteria rule as defined in NFPA 13 under “Obstructions to Sprinkler Discharge Pattern Development”.

• 

For installation under concrete tees when installed as follows: 

1. The stems of the concrete tee construction must be spaced between 3 ft (0.9 m) and 7 ft-6 in (2.3 m) on center. The depth of the concrete tees must 

not exceed 30 in (762 mm). The maximum permitted concrete tee length is 32 ft (9.8 m). However, where the concrete tee length exceeds 32 ft (9.8 

m), non-combustible baffles, equal in height to the depth of the tees, can be installed so that the space between the tees does not exceed 32 ft (9.8 m).

2. The sprinkler deflector is to be located in a horizontal plane at or above 1” (25.4 mm) below the bottom of the concrete tee stems.

3. When the sprinkler deflector is located higher than a horizontal plane 1” (25.4 mm) beneath the bottom of the concrete tee stems, the obstruc-

tion to sprinkler discharge criteria requirements of NFPA 13 for extended coverage upright sprinklers applies. 

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and 

also with the provisions of governmental codes, ordinances, and standards, whenever applicable.

Summary of Contents for 08687

Page 1: ...4 5 bar Factory tested hydrostatically to 500 psi 34 5 bar Thread size 3 4 20 mm NPT Nominal K Factor 11 2 U S 161 3 metric Metric K factor measurement shown is in Bar When pressure is measured in kPa...

Page 2: ...bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern...

Page 3: ...rinkler Finishes Brass Chrome White Polyester3 Black Polyester3 and ENT Corrosion Resistant Coatings4 ENT Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Ot...

Page 4: ...min 84 Bar D1 D2 16 ft x 16 ft 4 9 m x 4 9 m 256 ft2 23 8 m2 30 gpm 7 2 psi 113 6 L min 50 Bar B1 E2 18 ft x 18 ft 5 5 m x 5 5 m 324 ft2 30 1 m2 33 gpm 8 7 psi 124 9 L min 60 Bar B1 E2 20 ft x 20 ft...

Page 5: ...ly cULus Listed for Ordinary Hazard Occupancies For non combustible obstructed construction within trusses or bar joists having non combustible web members greater than 1 25 4 mm when applying the 4 t...

Page 6: ...When using 10 6 x 13 0 sprinkler spacing provide the Minimum Water Supply Requirement listed in the chart for 14 0 x 14 0 spacing For areas of coverage smaller than shown use the Minimum Water Supply...

Page 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Page 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Page 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Page 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Page 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...