background image

STANDARD/QUICK RESPONSE 

EXTENDED COVERAGE 

UPRIGHT SPRINKLER 

VK532 (K11.2)

TECHNICAL DATA

Page 4 of 6

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com

Form No. F_053114   19.10.14     Rev 19.1

Approval Chart 1 (UL)

SR/QR EC Upright Sprinkler VK532

Sprinkler Base

 

Part Number

1

SIN

NPT Thread Size

Nominal K-Factor

Maximum Water

 

Working Pressure

Overall Length

Inches

mm

U.S.

metric

2

Inches

mm

08687 Upright

VK532

3/4

20

11.2

161.3

175 psi (12 Bar)

2-5/16

59

Max. Sprinkler 

Spacing

 

(L x W

7

)

Maximum 

Area per 

Sprinkler

Minimum Water Supply Requirements

5

Listings and Approvals

3

(Refer also to UL Design

 

Criteria)

Light Hazard

Ordinary Hazard Group I

Ordinary Hazard Group II

Flow / Pressure

Flow / Pressure

Flow / Pressure

cULus

4

Standard Response

16 ft. x 16 ft. (4.9 

m x 4.9 m)

256 ft

2

 (23.8 

m

2

)

--

38 gpm @ 11.5 psi 

(143.9 L/min @ .79 Bar)

51 gpm @ 20.7 psi 

(193.1 L/min @ 1.43 Bar)

C1, C2

18 ft. x 18 ft. (5.5 

m x 5.5 m)

324 ft

2

 (30.1 

m

2

)

--

49 gpm @ 19.1 psi 

(185.5 L/min @ 1.32 Bar)

65 gpm @ 33.7 psi 

(246.1 L/min @ 2.32 Bar)

C1, C2

20 ft. x 20 ft. (6.1 

m x 6.1 m)

400 ft

2

 (37.2 

m

2

)

--

60 gpm @ 28.7 psi 

(227.1 L/min @ 1.98 Bar)

80 gpm @ 51.0 psi 

(302.8 L/min @ 3.52 Bar)

C1, C2

Quick Response

12 ft. x 12 ft. (3.7 

m x 3.7 m)

144 ft

2

 

(13.4 m

2

)

--

30 gpm @ 7.2 psi 

(113.6 L/min @ .50 Bar)

39 gpm @ 12.1 psi 

(147.7 L/min @ .84 Bar)

D1, D2

14 ft. x 14 ft. (4.3 

m x 4.3 m)

196 ft

2

 

(18.2 m

2

)

--

30 gpm @ 7.2 psi 

(113.6 L/min @ .50 Bar)

39 gpm @ 12.1 psi 

(147.7 L/min @ .84 Bar)

D1, D2

16 ft. x 16 ft. (4.9 

m x 4.9 m)

256 ft

2

 (23.8 

m

2

)

30 gpm @ 7.2 psi 

(113.6 L/min @ .50 Bar)

--

--

B1, E2

18 ft. x 18 ft. (5.5 

m x 5.5 m)

324 ft

2

 (30.1 

m

2

)

33 gpm @ 8.7 psi (124.9 L/

min @ .60 Bar)

--

--

B1, E2

20 ft. x 20 ft. (6.1 

m x 6.1 m)

400 ft

2

 (37.2 

m

2

)

40 gpm @ 12.8 psi (151.4 

L/min @ .88 Bar)

--

--

A1, F2

Approved Temperature Ratings

A - 135 °F (57 °C) and 175 °F (79 °C)
B - 135 °F (57 °C), 155 °F (68 °C), and 175 °F (79 °C)
C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)
D - 155 °F (68 °C)
E - 155 °F (68 °C), and 175 °F (79 °C)
F - 175 °F (79 °C)

Approved Finishes

1 - Brass, Chrome, White Polyester, and Black Polyester
2 - ENT

6

Footnotes

1

 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule.

2

 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

3

 This chart shows listings and approvals available at time of printing. Check with the manufacturer for any additional approvals.

4

 cULus Listed for use in the U.S. and Canada.

5

 To determine “Minimum Water Supply Requirement” for areas of coverage where length and width of actual sprinkler spacing are not equal, select the “Maximum 

Sprinkler Spacing” from the chart that is equal to or greater than the larger of the actual spacing (length or width) dimensions used. Example: When using 10’-6” x 

13’-0” sprinkler spacing, provide the “Minimum Water Supply Requirement” listed in the chart for 14’-0” x 14’-0” spacing. For areas of coverage smaller than shown, 

use the “Minimum Water Supply Requirement” in the appropriate hazard group for the next larger area listed. The distance from sprinklers to walls shall not exceed 

one-half the “Maximum Sprinkler Spacing” listed for the “Minimum Water Supply Requirement” used.

6

 cULus Listed as corrosion-resistant.

Summary of Contents for 08687

Page 1: ...4 5 bar Factory tested hydrostatically to 500 psi 34 5 bar Thread size 3 4 20 mm NPT Nominal K Factor 11 2 U S 161 3 metric Metric K factor measurement shown is in Bar When pressure is measured in kPa...

Page 2: ...bulb expands causing the glass to shatter releasing the pip cap and sealing spring assembly Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern...

Page 3: ...rinkler Finishes Brass Chrome White Polyester3 Black Polyester3 and ENT Corrosion Resistant Coatings4 ENT Footnotes 1 The sprinkler temperature rating is stamped on the deflector 2 Based on NFPA 13 Ot...

Page 4: ...min 84 Bar D1 D2 16 ft x 16 ft 4 9 m x 4 9 m 256 ft2 23 8 m2 30 gpm 7 2 psi 113 6 L min 50 Bar B1 E2 18 ft x 18 ft 5 5 m x 5 5 m 324 ft2 30 1 m2 33 gpm 8 7 psi 124 9 L min 60 Bar B1 E2 20 ft x 20 ft...

Page 5: ...ly cULus Listed for Ordinary Hazard Occupancies For non combustible obstructed construction within trusses or bar joists having non combustible web members greater than 1 25 4 mm when applying the 4 t...

Page 6: ...When using 10 6 x 13 0 sprinkler spacing provide the Minimum Water Supply Requirement listed in the chart for 14 0 x 14 0 spacing For areas of coverage smaller than shown use the Minimum Water Supply...

Page 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Page 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Page 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Page 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Page 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Reviews: