3-9.4 Auto
Checking
This page allows the user to specify the auto detection parameters to check the
linking status between PoE ports and PDs. When it detects the fail connection, it will
reboot the remote PD automatically.
Web Interface
To display Power over Ethernet Auto Checking in the web interface:
1.
Click Configuration, PoE, and Auto checking.
2.
Enable the “Ping Check” function.
3.
Specify the PD’s IP address, checking interval, retry time, failure action, and
reboot time.
4.
Click “Apply” to apply the change.
Figure 3-9.4: The POE Auto Checking
CAUTION:
When using PoE to power an IP camera or
similar device that goes through an initialization period,
do not set the "Interval Time" below 20 seconds if the
"Failure Action" is set to "Reboot Remote PD". Doing
so may prevent the switch from successfully pinging the
device and result in a continuous ON-Off-ON-OFF cycle
of the PoE power.