background image

TS21I_ELE_O2 User Manual 

Page 

6

 of 

14

                       

 

 

Make the connections for relay and RS 485 as mentioned in above table. 

 

Take out wires from output and connect it to desired instrument.      

 

Insert power adapter to the mains socket. 

 

Operation 

 

When unit is powered ON, it goes in to an initial warm up period of 20 seconds. After this period is 
over, unit enters into scan mode when it continuously monitors gas concentration level in the 
atmosphere. When gas concentration exceeds low or high alarm threshold levels, relay output 
changes accordingly. It shows gas concentration level between 0 and 30 % vol. with LED indication 
on front panel. TS21I_ELE_O2 has two settable alarm levels. Low alarm level and High alarm level.  
Fault Relay operate on supply voltage below 18V or more than 29V and also according to sensor 
open or short with LED indication on front panel. 
 
It uses four magnetic keys which operate using single magnetic stylus to do settings like low / high 
alarm levels, relay output type and so on.  
 
Front panel of typical TS21I_ELE_O2 is shown as below. 
 

 

Relay Settings

 
TS21I_ELE_O2 has three relay outputs.  
Relay1 is for low alarm condition, Relay2 is for high alarm condition and Relay3 is for Fault 
operation.  
User can use it as a NO or NC type output using the respective jumper adjustments. User can set 
relay output type for both relays as PULSE type or LATCH type.  
Pulse type output: Relay trips for 5 sec and comes back to its previous state.  
Latch type output: Relay remains latched till the unit is reset. 
If unit is connected to a Gas Detection Panel,

 

using MODBUS communication, the Gas Detection 

Panel gives an alert depending on the status of TS21I_ELE_O2.  
 

Summary of Contents for TrueSafe TS21I ELE O2

Page 1: ...te http www vighnaharta in Prepared By Megha C Approved By Jeetendra G Doc No TS21I_ELE_O2_UM_1_0 Rev No 1_1 Eff Date 01 Aug 2018 TS21I_ELE_O2 USER MANUAL Mfg By Vighnaharta Technologies Pvt Ltd 2nd Floor Karanjkar Estate S N 11 11 Nanded Gaon Pune 411041 Contact no 919011033259 Landline Sales 919011033260 Email sales vighnaharta in Website http www vighnaharta in ...

Page 2: ...I_ELE_O2 User Manual Page 2 of 14 Table of Contents Overview III Technical Specifications IV Installation Procedure IV Operation VI Menus available in TS21I_ELE_O2 X Calibration process for TS21I_ELE_O2 XI ...

Page 3: ...ol with user defined high and low alarm level Four digit seven segment LED display for Vol indication 3 potential free relay output with user selectable NO NC Digital input for gas valve status feedback only for Modbus monitoring Four magnetic keys which can be operated using magnetic stylus RS485 port for networking multiple gas detectors to building management system Supports MODBUS RTU protocol...

Page 4: ... installed at about five feet from ground If fastest possible gas leak detection is required the sensor should be mounted near the potential leak sources Packing List TS21I_ELE_O2 unit Power supply adapter Optional mounting screws User manual Screw driver Allen Key set To install the unit at the user premises 1 Run all desired power siren and hardware contact wires to the panel location 2 Level th...

Page 5: ...wer loads through the relay use only as potential free contacts Connector Details of the unit Connector CON1 Pin No Description 1 R1COM Relay 1 common 2 R1NO Relay 1 NO 3 R2COM Relay 2 common 4 R2NO Relay 2 NO 5 R3COM Relay 3 common 6 R3NO Relay 3 NO Connector CON2 Pin No Description 1 D RS 485 data 2 D RS485 data 3 C ve current Output 4 C ve current Output 5 A O P ve analog output voltage 6 A O P...

Page 6: ... supply voltage below 18V or more than 29V and also according to sensor open or short with LED indication on front panel It uses four magnetic keys which operate using single magnetic stylus to do settings like low high alarm levels relay output type and so on Front panel of typical TS21I_ELE_O2 is shown as below Relay Settings TS21I_ELE_O2 has three relay outputs Relay1 is for low alarm condition...

Page 7: ... output will be NO type Jumper between pin 2 and 3 Relay2 output will be NC type JP2 For Relay3 JP3 Jumper between pin 1 and 2 Relay3 will be NO type Jumper between pin 2 and 3 Relay3 will be NC type JP3 Modbus Settings The following connection diagram shows TS21I_ELE_O2 units connected with Gas Detection Panel Siren and power connector locations are shown as below Addresable Gas Detection Panel A...

Page 8: ...Even Parity Relay 1 NO O P PULSE type Relay 2 NO O P PULSE type Relay 3 NO O P PULSE type Output Voltage 0 10Volts Understanding controls on front panel LED Indicators 1 ON Power ON LED Green LED turns on when power is ON It indicates Power On status of the unit 2 L Alarm When gas concentration exceeds low threshold level TS21I_ELE_O2 generates low alarm condition For low alarm condition yellow LE...

Page 9: ...netic Keypad Four magnetic keys operate using magnetic stylus 1 ENTER Move stylus to ENTER key to enter into system to access menus This key has dual function It is used to Enter or Save the data User can select some menu or can save settings made by the user If user presses the key during Idle mode it displays the menu 2 ESCAPE Move stylus to ESCAPE key to exit from the current menu If user exits...

Page 10: ...tion 3 To go into oP L function again press ENTER key 4 Use Up and Down keys to select PULSE or LATCH type for Relay1 output 5 Press Enter key to save the settings or press Escape key to return to previous menu without saving the settings 4 oP h Output High User can set Relay2 output as either PULSE or LATCH type 1 Press ENTER to go in main menu 2 Use Down key to select oP h function 3 To go into ...

Page 11: ...ot stop giving gas to sensor until settings are saved 5 Press ESCAPE key to exit from configuration mode and remain in Idle or Scan mode 3 23 5 23 5 vol calibration This is a calibration function used to calibrate sensor for 23 5 vol gas This menu must be used only when the unit is in clean atmosphere It displays raw sensor data on seven segment display 1 Go to menu 23 5 2 Use 23 5 vol concentrati...

Page 12: ... mode 6 bAUd User can set baud rate either 2400 9600 19200 1 Press ENTER to go in main menu 2 Use Down key to select bAUd function 3 To go into bAUd function again press ENTER key 4 Use Up or Down keys to select any one baud rate from following option 2 4 2400 9 6 9600 19 2 19200 5 Press Enter key to save the settings or press Escape key to return to previous menu without saving the settings 7 PAr...

Page 13: ...or will not respond For this reason it is absolutely essential that these sensors be calibrated on a regular basis Typical sensor life will be two years The new sensor can be span calibrated immediately however an 8 hour warm up period is required before zeroing if necessary Disclaimer for TrueSafe All statements technical information and recommendations contained herein are based on available sci...

Page 14: ...arranty in no case shall extend to any monetary consideration whatsoever 3 The cost of to and fro transportation of TrueSafe to the nearest service center will be borne by the purchaser 4 The warranty will be void if a The damage is caused by accident flood fire misuse negligence or erratic voltage fluctuation b If service or repair has been attempted by persons not authorized by the company 5 All...

Reviews: