Parameter 08: Bypass hysteresis
This setting determines the tempera-
ture differential (hysteresis) at which
the bypass damper is switched elec-
tronically.
Permitting a pressure imbalance
Set value "2" for parameter 08, as
described on page 34.
Standard setting:
2
Setting range:
0 to 5
Parameter 09: Constant pressure switched OFF
This setting determines whether the
ventilation air and extract air device
safeguards a constant flow rate or
maintains a constant pressure from a
specific pressure drop onwards.
We recommend to leave the setting at
"0" (0= constant flow rate).
"Constant flow rate"
Set value "0" for parameter 09, as
described on page 34.
"Constant pressure"
Set value "1" for parameter 09, as
described on page 34.
Standard setting:
0
Setting range:
0 to 1
Parameter 10: Filter change
This setting determines whether the
display of the remote control will indi-
cate the need for a filter change.
We recommend to leave the setting at
"0" (= filter change indicator ON).
"Indicate filter change"
Set value "1" for parameter 10, as
described on page 34.
"No filter change indication"
Set value "0" for parameter 10, as
described on page 34.
Standard setting:
1
Setting range:
0 to 1
Remote control settings by contractors
(cont.)
37
Remote control settings
5692
762
GB
Summary of Contents for VITOVENT 300
Page 44: ...Version 180 m3 h Parts list cont 44 Parts list 5692 762 GB...
Page 46: ...Version 300 and 400 m3 h Parts list cont 46 Parts list 5692 762 GB...
Page 47: ...List of control parameters 47 Commissioning service reports 5692 762 GB...
Page 48: ...Commissioning report example 48 Commissioning service reports 5692 762 GB...