A
Aperture width of the annular gap
[mm]
B
Sector plate
1.
Determine the width of the air inlet
using the intended flow rate and the
specified pressure drop from the
following diagram.
2.
Adjust the air inlet in accordance
with the calculated aperture width.
3.
Record the actual value in the com-
missioning report.
Example:
Calculate the annular gap at a pres-
sure drop of
Δ
p
s
= 20 Pa:
Air flow rate (acc.
to design):
q
v
= 48 m
3
/h
Annular gap:
6 mm
Further details regarding the individual steps
(cont.)
11
Commissioning, inspection, maintenance
5692
762
GB