![Viessmann VITOVENT 300 Service Instructions For Contractors Download Page 20](http://html1.mh-extra.com/html/viessmann/vitovent-300/vitovent-300_service-instructions-for-contractors_1017789020.webp)
Checking the air velocity
A
Extract air valve
B
Measuring funnel
C
Impeller air speed meter
D
Measurement at the floor outlet
1.
Measure the air flow rate (observe
the instructions of the test equip-
ment manufacturer).
Note
Use a measuring funnel in ventila-
tion air and extract air apertures, in
the cross-section of which the air
velocity or air flow rate is measured
with an impeller air speed meter.
Where a measuring funnel cannot
be used, for example in larger ven-
tilation air or extract air apertures
(such as in floor outlets) - carry out
several measurements over an
area and calculate an average
value.
2.
Record the actual value in the com-
missioning report.
Air flow rate curves
1.
Using the actual air velocity, check
the air flow rates from the curve
diagrams.
2.
Record the actual values in the
commissioning report.
Further details regarding the individual steps
(cont.)
20
Commissioning, inspection, maintenance