Readjusting the air flow rates
1.
Determine the deviation between
the design and the actual air flow
rates.
2.
Readjust the air inlets/outlets in
proportion to the deviation.
3.
Record the readjusted aperture
widths in the commissioning report.
4.
Carry out a second measurement
and check the readjustment.
5.
Fix the air inlets/outlets after the
final adjustment (if necessary fix
with a locknut).
6.
Determine the air flow rates from
the curve diagrams on page 21 or
from the table on page 14 and
record the values in the commis-
sioning report.
Shutting down the system
1.
Set the program selector of the
remote control to standby "
9
".
2. Only when working on an open
appliance:
Danger
Touching 'live' components
can result in the transfer of
dangerous body currents.
Prior to working on the appli-
ance
pull the power plug
and prevent accidental
reconnection
.
Further details regarding the individual steps
(cont.)
22
Commissioning, inspection, maintenance