16
A
Fig. 9
1.
Blow through the water level indicator.
2.
Remove upper locking screw
A
and clean the
water level indicator with a brush.
See documentation for the water level indi-
cator.
Checking the hydraulic connections for leaks
Checking all connections on the water and steam side, as well as the sensor well and the inspection
ports, for leaks after filling the boiler
A
Fig. 10
1.
Each time inspection ports have been opened:
Clean the sealing face.
2.
Replace the gasket.
3.
Retighten all covers after commissioning.
4.
For testing the sensor well, remove cover
A
.
Cleaning the sight glass in the boiler door
Fig. 11
Check the gaskets and hose connection for leaks.
Commissioning, inspection, maintenance
Cleaning the water level indicator