
83
Example using the settings in the delivered condition
10
0
20
30
30
40
50
60
6
00
7
00
8
00
9
00
Set boiler water or flow temperature in °C
Time in h
A
B
C
D
A
Start of operation with standard
room temperature
B
Set boiler water or flow temperature
in accordance with the selected
heating curve
C
Set boiler water or flow temperature
in accordance with coding address
"FA":
50 °C + 20 % = 60 °C
D
Duration of operation with raised set
boiler water or flow temperature in
accordance with coding address
"Fb":
60 min
Remote control DIP switches
The DIP switches are located on the PCB in the top part of the casing.
Function description
Control functions
(cont.)
5692 774 GB