23
Note
Refit in reverse order.
Checking the condensate drain and cleaning the siphon (if instal-
led)
1.
Check at siphon (see page 9), that
the condensate can freely drain off.
2.
Clean the siphon.
3.
Fill the siphon with water.
Checking the neutralising system (accessories)
Subject to a neutralising system being housed in the boiler plinth:
■ Remove the front cover from the plinth.
■ Extract the neutralising system from the plinth.
■ When installing the neutralising system ensure that the hoses are not kinked, and
that no backup loops are created.
Check the function of the neutralising
system:
Check the pH value of the condensate
with pH test strips.
Replace the granulate if the pH value
< 6.5.
Note
Part no. for pH test strips: 9517 678.
Please observe the instructions of the
manufacturer of the neutralising sys-
tem.
Checking the active charcoal filter (accessories)
Note
Please observe the instructions of the manufacturer of the active charcoal filter sup-
plied.
Adjusting the standard burner settings
Note
To be able to adjust the burner, there
must be a heat demand and heat trans-
fer must also be assured.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5692 774 GB