Coding in the delivered condition
Possible change
b0:0
With remote control:
Heating mode/reduced
mode: Weather-compen-
sated
*1
b0:1
Heating mode: Weather-
compensated
Reduc. mode: With room
temperature hook-up
b0:2
Heating mode: With room
temperature hook-up
Reduc. mode: Weather-
compensated
b0:3
Heating mode/reduced
mode: With room tempera-
ture hook-up
b2:8
With remote control and
for the heating circuit,
operation with room tem-
perature hook-up must be
programmed: Room influ-
ence factor 8
*1
b2:0
Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0
With remote control: No
room temperature-
dependent heating circuit
pump logic function
(change the coding only
for the heating circuit with
mixer M2)
*1
b5:1
to
b5:8
Heating circuit pump logic
function, see the following
table:
Parameter
address b5:...
With heating circuit pump logic function: Heating circuit
pump OFF, if
1:
enabled RT
actual
> RT
set
+ 5 K; disabled RT
actual
< RT
set
+ 4 K
2:
enabled RT
actual
> RT
set
+ 4 K; disabled RT
actual
< RT
set
+ 3 K
3:
enabled RT
actual
> RT
set
+ 3 K; disabled RT
actual
< RT
set
+ 2 K
4:
enabled RT
actual
> RT
set
+ 2 K; disabled RT
actual
< RT
set
+ 1 K
5:
enabled RT
actual
> RT
set
+ 1 K; disabled RT
actual
< RT
set
6:
enabled RT
actual
> RT
set
; disabled RT
actual
< RT
set
- 1 K
7:
enabled RT
actual
> RT
set
- 1 K; disabled RT
actual
< RT
set
- 2 K
8:
enabled RT
actual
> RT
set
- 2 K; disabled RT
actual
< RT
set
- 3 K
*1
Change the code for the heating circuit without mixer A1 or for the heating circuit
with mixer M2 only, if the remote control unit affects that heating circuit.