33
Rated heating output of the boiler
T
F
/T
R
= 50/30
°
C
kW
67.6
85.8
107.3
T
F
/T
R
= 80/60
°
C
kW
63
80
100
Oil burner nozzle
Make: Danfoss
Type
80
°
H
80
°
H
80
°
H
Gph
1.0
1.35
1.75
Oil pressure
approx.
*2
Stage 1
bar min.
12.5
11.0
12.5
Stage 2
bar
24.0
21.0
20.0
Oil throughput
Stage 1
kg/h
3.6
4.9
6.2
l/h
4.6
5.7
7.2
Stage 2
kg/h
5.5
7.0
8.8
l/h
6.5
8.2
10.3
Position of the switching cams at the air damper
servomotor
*3
SL
°
8
11
10
ST 1
°
9
12
11
ST 2
°
50
50
50
BV
°
30
30
30
Inlet air aperture setting
5
5
5
Static burner pressure
*4
Stage 1
mbar
12.0
15.5
15.5
Stage 2
mbar
22.5
25.5
22.5
*2
Due to nozzle tolerances and varying oil characteristics, the oil pressure may vary from the specified values.
*3
The air damper servomotor is factory-set and must only be adjusted in exceptional cases. Exceptions are the replacement
of the air damper servomotor, soot build-up and the altitude above sea level of the installation site.
The CO
2
value must only be adjusted by regulating the oil pressure.
*4
Standard values for checking the burner adjustment.
Standard values for burner adjustment
Standard values for burner adjustment
5831447