Initial Start-up, Inspection and Maintenance
56
Steps
(continued)
15. Check condensate drain and clean siphon (P-trap)
S
ervice
Maintenance
1.
Check the siphon to ensure
unimpeded drainage of condensate.
2.
Place appropriate container
underneath siphon
.
3.
Remove sealing cap
and drain
siphon content into the container.
4.
Replace the sealing cap
w/gasket.
5.
Fill the siphon
with water by
pouring 10 fl.oz. / 0.3L of water into
the combustion chamber.
If the condensate does not drain freely,
condensate will accumulate in bottom
part of boiler resulting in a burner
shut-down (fault message F4). The
combustion chamber refractory will
also become wet at the bottom
portion. Do not restart the boiler
immediately with a wet combustion
chamber refractory. This will damage
the refractory. Either dry the refractory
or replace it.
Installation Instructions
Neutralization Unit
(if applicable)
16. Check neutralization unit
(if applicable)
Accessory
S
ervice
Maintenance
1.
Check the pH value of the
condensate with a pH measuring
strip. If the pH value is less than
6.5, replace granulate.
pH measuring strip is field supplied.
2.
If contaminated:
Rinse neutralization unit with tap
water.
3.
Add granulate as marked.
The granulate is consumed as it
neutralizes the condensate. The red
marking indicates the min. filling level.
Installation Instructions
Neutralization Unit
5
5
8
1
7
7
5
1
.3
A
B
IMPORTANT