Boiler Connections
23
Connections
(continued)
Condensate connection
Flexible discharge tubing
Discharge tubing
The Vitodens 100-W boiler comes with
a built-in condensate trap. An external
trap is not required when connecting
the field drain to flexible discharge
tubing. Discharge tubing (field supplied)
must be of 1” diameter. Use CPVC,
PVC or other material approved by
codes listed below.
In the U.S. the drain pipe and fittings
must conform to ANSI standards and
ASTM D1785 or D2846. CPVC or PVC
cement and primer must conform to
ASTM D2564 or F493. In Canada use
CSA or ULC listed schedule 40 CPVC
or PVC drain pipe, fittings and cement.
If the condensate outlet of the
Vitodens 100-W boiler is lower than
the drain, a condensate pump must be
installed. Select a pump which is
approved for condensing boiler
applications. To avoid condensate
spillage, select a pump with an
overflow switch. The drain connection
must terminate into an open or vented
drain as close to the boiler as possible
to prevent siphoning of the boiler drain.
1.
Install the condensate drain pipe
with a suitable gradient.
2.
Discharge condensate from the
boiler into the drainage system,
either directly or (if required) via a
neutralization unit (accessory).
Installation Instructions of
Neutralization Unit
(if applicable)
Pipe ventilation must take place
between the siphon trap and the
neutralization unit (if applicable).
Do not connect the drain pipe from any
other appliance, such as water softener
backwash pipe, to Vitodens
condensate drain pipe.
Fill Siphon with water
Fill a minimum of 10 fl.oz. / 0.3 liters
of water into the boiler adaptor.
5
5
8
1
7
7
5
1
.3
IMPORTANT
IMPORTANT
At initial start-up, flue gases may be
emitted from the condensate drain.
Fill the siphon with water before
start-up.
WARNING