Vitodens 100-W, B1HA series & B1KA Combi Installation/Service
Boiler mounting frame dimensions
The boiler stand is used for free-standing installation of
a single boiler within the mechanical room.
When using the boiler stand, ensure that the stand is
securely fastened to the floor (recommended concrete
expansion anchors are Hilti model KB-TZ
e
x 4 or
equivalent.
The Vitodens 100-W, does not come with a mounting
template. The wall location for the frame, mounting
bracket and all vents must be field calculated.
Boiler mounting bracket and frame
1. Attach the wall mounting bracket (supplied with the
boiler) to the boiler mounting frame using the supplied
hardware. Ensure that the wall mounting bracket is
level.
2. Move the rack into position and secure to the floor
(and to the wall if needed).
Boiler Mounting
(continued)
CAUTION
The boiler must be level both vertically and horizontally
to ensure proper draining of the condensate.
Installation
Refer to the single boiler rack Installation
Instructions for more details.
Vitodens 100-W, B1HA 26, 35, B1KA 35
a *
1
in. (mm)
45
f
(1160)
b *
1
in. (mm)
77
c
(1975)
c in. (mm)
17
c
(450)
d in. (mm)
1
a
(33)
e in. (mm)
79 (2007)
*
1
K
b
in. (12.7 mm) for adjustment of the levelling feet.