31
Connecting the neutralising system
A
B
D E
C
Fig. 28
Installation and operating instructions for neu-
tralising system
1.
Position neutralising system
A
either behind or
next to the boiler.
2.
Mount trap
C
(supplied with the boiler) and fill with
water.
3.
Trim plastic hose
B
supplied to the required size
and connect it to stench trap
C
and neutralising
system
A
.
Danger
Flue gas escaping from the trap or conden-
sate drain can cause life threatening carbon
monoxide poisoning.
To prevent flue gas from escaping,
always
connect the condensate drain with a trap.
Always fill the siphon with water
before
commissioning.
4.
Connect drain hose
D
to the condensate drain of
the neutralising system and route to drainage sys-
tem
E
.
Commissioning and adjustment
Service instructions for boiler and boiler control
unit
Note
Adjust the gas throughput of the burner according to
the rated boiler heating output.
Note
For safe operation, a minimum operating pressure of
0.5 bar/50 kPa is required.
If required, use a minimum pressure limiter.
Connections on the flue gas side
(cont.)
5833527