78
5
Fig. 33
1. Cylinder temperature sensor
Pull out plug
%
. Measure the resistance.
2.
Check sensor resistance and compare it to the
curve.
10
1
10
30
50
70
90
110
Temperature in °C
0.4
0.6
0.8
2
4
6
8
20
Resistance
in kΩ
Fig. 34
Sensor type: NTC 10 k
Ω
3.
In the event of severe deviation replace the sensor.
Checking the boiler water temperature sensor
Note
The boiler water temperature sensor is a dual sensor.
A
Fig. 35
1. Boiler water temperature sensor
Pull plug and measure the resistance.
Maintenance
Checking the cylinder temperature sensor
5792 925 GB
Maintenance
Summary of Contents for Vitocrossal 100 CI1
Page 138: ...138 5792 925 GB ...