67
Fault code dis-
played
System characteristics
Cause
Measures
B0
Burner blocked
Short circuit, flue gas tem-
perature sensor
Check flue gas temperature sen-
sor.
B1
Control mode as per deliv-
ered condition
Communication error, pro-
gramming unit
Check connections; replace pro-
gramming unit if necessary.
B5
Control mode as per deliv-
ered condition
Internal fault
Replace control unit.
B7
Burner blocked
Fault, coding card
Plug in coding card or replace if
faulty.
B8
Burner blocked
Lead break, flue gas tem-
perature sensor
Check flue gas temperature sen-
sor.
BA
Mixer regulates to 20 °C flow
temperature.
Communication error, ex-
tension kit for heating cir-
cuit 2 (with mixer)
Check extension kit connections
and code.
BB
Mixer regulates to 20 °C flow
temperature.
Communication error, ex-
tension kit for heating cir-
cuit 3 (with mixer)
Check extension kit connections
and code.
BC
Control mode without remote
control
Communication error,
Vitotrol remote control,
heating circuit 1 (without
mixer)
Check connections, cable and cod-
ing address
"A0"
in the
"Heating
circuit"
group and the remote con-
trol settings. For wireless remote
control units: Check connection;
place remote control close to the
boiler.
BD
Control mode without remote
control
Communication error,
Vitotrol remote control,
heating circuit 2 (with mix-
er)
Check connections, cable and cod-
ing address
"A0"
in the
"Heating
circuit"
group and the remote con-
trol settings. For wireless remote
control units: Check connection;
place remote control close to the
boiler.
BE
Control mode without remote
control
Communication error,
Vitotrol remote control,
heating circuit 3 (with mix-
er)
Check connections, cable and cod-
ing address
"A0"
in the
"Heating
circuit"
group and the remote con-
trol settings. For wireless remote
control units: Check connection;
place remote control close to the
boiler.
BF
Control mode
Incorrect LON communi-
cation module
Replace LON communication mod-
ule.
C1
Control mode
Communication error, EA1
extension
Check connections.
C2
Control mode
Communication error, so-
lar control module or
Vitosolic
Check solar control module or
Vitosolic.
C3
Control mode
Communication error,
AM1
Check connections.
CF
Control mode
Communication error,
LON communication mod-
ule
Replace LON communication mod-
ule.
D6
Control mode
Input DE1 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
D7
Control mode
Input DE2 at EA1 exten-
sion reports a fault.
Remedy fault at appliance con-
cerned.
Troubleshooting
Fault codes
(cont.)
5792 925 GB
Diagnosis
Summary of Contents for Vitocrossal 100 CI1
Page 138: ...138 5792 925 GB ...
Page 139: ...139 5792 925 GB ...