24
2.
Pull the neutralising system out from under the
boiler, from the front.
To remove front panel, see page 11.
3.
"Neutralising system" installation and service
instructions
Note
With twin boilers, the neutralising system is positioned
behind the boiler.
Twin boiler
B
D
E
A
C
Fig. 18
A
Drain hose from trap to neutralising system
B
Drain hose from flue gas header to neutralising
system
C
Neutralising system
D
Drain hose from neutralising system to drainage
system
E
Checking the condensate drain and neutralising system (if installed) for
obstructions and leaks
Fill the combustion chamber with water.
Note
The water must flow from the condensate drain pipe
without backing up.
If necessary, clean the condensate drain pipe again.
Commissioning, inspection, maintenance
Cleaning the neutralising system (if installed)
(cont.)
5792 925 GB