71
Fault code dis-
played
System characteristics
Cause
Measures
FE
Burner blocked or in a fault
state
Coding card or main PCB
faulty, or incorrect coding
card
Press reset button
R
. If fault per-
sists, check the coding card and
replace coding card or control unit
if necessary.
FF
Burner blocked or in a fault
state
Internal fault or reset but-
ton
R
blocked.
Restart the appliance. Replace the
control unit if the appliance will not
restart.
10
Regulates as if the outside
temperature were 0 °C.
Short circuit, outside tem-
perature sensor
Check outside temperature sensor
(see page 77).
18
Regulates as if the outside
temperature were 0 °C.
Lead break, outside tem-
perature sensor
Check outside temperature sensor
(see page 77).
19
Regulates as if the outside
temperature were 0 °C.
Communication interrup-
tion, wireless outside tem-
perature sensor
Check wireless connection (place
wireless outside temperature sen-
sor close to the wireless base sta-
tion). Forget outside temperature
sensor, then pair again.
Wireless base station instal-
lation and service instruc-
tions
Replace wireless outside tempera-
ture sensor.
20
Regulates without flow tem-
perature sensor (low loss
header)
Short circuit, system flow
temperature sensor
Check the low loss header sensor
28
Regulates without flow tem-
perature sensor (low loss
header)
Lead break, system flow
temperature sensor
Check the low loss header sensor.
If no low loss header sensor is
connected, set code 52:0.
30
Burner blocked
Short circuit, boiler water
temperature sensor
Check boiler water temperature
sensor (see page 78)
38
Burner blocked
Lead break, boiler water
temperature sensor
Check boiler water temperature
sensor (see page 78)
40
Mixer is being closed.
Short circuit, flow temper-
ature sensor, heating cir-
cuit 2 (with mixer)
Check flow temperature sensor.
44
Mixer is being closed.
Short circuit, flow temper-
ature sensor, heating cir-
cuit 3 (with mixer)
Check flow temperature sensor.
48
Mixer is being closed.
Lead break, flow tempera-
ture sensor, heating circuit
2 (with mixer)
Check flow temperature sensor.
4C
Mixer is being closed.
Lead break, flow tempera-
ture sensor, heating circuit
3 (with mixer)
Check flow temperature sensor.
50
No DHW heating
Short circuit, cylinder tem-
perature sensor
Check sensors (see page 78).
58
No DHW heating
Lead break, cylinder tem-
perature sensor
Check sensors (see page 78).
90
Control mode
Short circuit, temperature
sensor
/
Check sensor
/
on solar control
module.
91
Control mode
Short circuit, temperature
sensor
aÖ
Check sensor
aÖ
on solar control
module.
Troubleshooting
Fault codes
(cont.)
5792 925 GB
Diagnosis