Product Installation

½’’

ID

1

5

ID

1

9

.2

A

F

2

4

220

8

The Vitocell-H 100 tank is approved for
heating systems with a maximum DHW
supply of up to 150 °F / 65.6 °C only

.

Sensor Well

Vitocell-H 100,
with 42 and 53 USG / 160 and 200 ltr
capacity

Vitocell-H 100 domestic hot water
tank positioned under the boiler

Please note that only the boiler/tank
combinations stated in the Price List are
possible.

Backflow preventers

Where backflow preventers are required, a
domestic water expansion tank installation
is recommended in the cold water inlet
piping before the cold water enters the
Vitocell. For the backflow device, observe
local plumbing codes and regulations.

Temperature and pressure
relief valve

A temperature and pressure relief valve
(T&P relief valve) is supplied with the tank.
The heating contractor must install the valve
on each tank in a method meeting code
requirements. If local codes require a
different relief valve, substitute the valve
supplied by the manufacturer. The tank is
approved for 150 psig. Maximum operating
pressure is 150 psig.

The T&P relief valve supplied with the tank
is tested under ANSI Z21.22 code for Relief
Valves and Automatic Gas Shut-off Devices
for Hot Water Supply Systems.

Since the heat exchanger coil allows for
high MBH input (see Vitocell flow charts),
confirmation that the appropriate and
correct size pressure and temperature relief
valve is used and installed, is necessary.

Watts Model
40XL-8

150 psig
(US and Canada)

ASME pressure
steam rating

1438 MBH

CSA temperature
steam rating

205 MBH

Relief
temperature

210ºF (99ºC)

Inlet thread

¾” male

Outlet thread

¾” female

Warranty

Our warranty for domestic hot water tanks
states that the water heated must be of
drinking water quality and that any water
treatment equipment in use must function
correctly.

Viessmann accepts no responsibility for
damage howsoever caused and reserves the
right to withdraw the product warranty if
the product has been improperly installed or
misapplied by the installer, contractor or
final user. In order to qualify for product
warranty, strict adherence to the installation
and service manuals must be assured. In the
event that Viessmann non-approved
components are utilized, Viessmann
reserves the right to withdraw all expressed
or implied warranties without written notice.

The water to be heated with the Vitocell
must be drinking (potable) water quality. If
the tank is used to heat other media, the
warranty will be null and void. Damage
resulting from excessive pressure or
temperature is clearly not the responsibility
of Viessmann.

The amount of chloride and sulfate
acceptable to the tank is limited. In areas
where high concentrations of chloride and
sulfate are present in drinking water, please
consult Viessmann for directions.

5

1

6

7

5

1

3

v

1

.4

IMPORTANT

To ensure optimum, safe operation,
the supplied stainless steel well must
be installed. The well diameter is
large enough to accommodate a wide
variety of sensing bulbs.

Always use spring clip to ensure
proper contact of capillary bulb
against the stainless steel well for
proper sensing/heat transfer!

WARNING

IMPORTANT

Summary of Contents for VITOCELL-H 100

Page 1: ...ect fired domestic hot water storage tank 42 and 53 USG 160 and 200 ltr 5167 513 v1 4 01 2012 Technical Data Manual Model Nos and pricing see Price List Vitocell H 100 CHA Series Enameled indirect fired domestic hot water storage tank steel construction with Ceraprotect two coat enamel finish ...

Page 2: ...Corrosion protected steel tank shell with Ceraprotect two coat enamel finish produced in house Magnesium anode provides additional cathodic tank protection H Heat exchanger coil extends to the bottom of the tank thereby heating the entire water content H Extremely convenient domestic hot water supply assured by fast uniform heating via generously sized heat exchanger surfaces H Standby losses mini...

Page 3: ... place clean out opening HCFC free insulation Non finned tubular heat exchanger coil extends to tank bottom the entire water volume is heated preventing cold spots Tank is constructed of steel with Ceraprotect two coat enamel finish Product may not be exactly as illustrated 5167 513 v1 4 ...

Page 4: ... 412 99 2 2 498 and heating water supply temperature of at the supply flow rate stated below 158 F 70 ºC MBH GPM ltr h 58 1 3 292 65 1 4 326 Supply flow rate for the recovery GPM m3 h 13 2 3 0 13 2 3 0 rates stated Standby losses 2 MBH 24 h 4 8 5 1 Overall dimensions Overall length inches mm Overall width inches mm Overall height inches mm 41 1052 25 640 25 654 47 1216 25 640 25 654 Weight Tank wi...

Page 5: ...O Inspection and Clean out Opening TPV Temperature and Pressure Relief Valve Overall height Overall width Overall length b DCW BWR IO 4 119 mm 2 63 mm 1 37 mm 6 167 mm 4 109 mm 12 311 mm 13 336 mm 18 459 mm AQ DHW and TPV BWS CA a 1 36 mm 5 Dimensions Storage capacity USG ltr 42 160 53 200 a inches mm 34 866 40 1030 b inches mm 9 250 11 300 5167 513 v1 4 ...

Page 6: ...PM 400 1000 w c mbar 44 10 000 16 40 20 50 24 60 32 80 40 100 80 200 120 300 160 400 200 500 240 600 320 800 1 6 4 2 5 2 4 6 3 2 8 4 10 8 20 12 30 1 2 3 2 2 500 2 6 600 3 5 800 4 4 1 000 9 2 000 13 3 000 18 4 000 22 5 000 26 6 000 35 8 000 Pressure drop Waterflow ltr min GPM 40 100 w c mbar 1 2 3 1 6 4 2 5 2 4 6 3 2 8 4 10 10 3 8 20 12 30 16 40 20 50 24 60 32 80 167 44 133 35 100 26 83 22 67 18 50...

Page 7: ...or well with insulation thermometer Installation Operating Start up and Service Instructions Product Installation This is a simplified conceptual drawing only Piping and necessary componentry must be field verified Proper installation and functionality in the field are the responsibility of the heating contractor Domestic hot water connections Domestic hot water DHW recirculation line DHW recircul...

Page 8: ...nd Canada ASME pressure steam rating 1438 MBH CSA temperature steam rating 205 MBH Relief temperature 210ºF 99ºC Inlet thread male Outlet thread female Warranty Our warranty for domestic hot water tanks states that the water heated must be of drinking water quality and that any water treatment equipment in use must function correctly Viessmann accepts no responsibility for damage howsoever caused ...

Page 9: ...Vitocell H 100 Sizing Continuous Flow Capacity Chart 9 Vitocell H 100 42 USG 160 ltr capacity Curve Domestic hot water 40 to 113 F 4 to 45 C Curve Domestic hot water 40 to 140 F 4 to 60 C 5167 513 v1 4 ...

Page 10: ...Vitocell H 100 Sizing Continuous Flow Capacity Chart 10 Vitocell H 100 53 USG 200 ltr capacity Curve Domestic hot water 40 to 113 F 4 to 45 C Curve Domestic hot water 40 to 140 F 4 to 60 C 5167 513 v1 4 ...

Page 11: ...gonal line used to size the pump The diagonal line begins at the origin and goes through the point of intersection extending up to the top of the chart Read between the reference diagonal lines to get a pump specification of 8 4 GPM at 1 7 ft To summarize For a Vitocell H 100 with 53 USG 200 ltr capacity and 119 MBH input the boiler water temperature is 194 F 90 C difference between boiler return ...

Page 12: ...ssmann ca info viessmann ca Viessmann Manufacturing Company U S Inc 45 Access Road Warwick Rhode Island 02886 USA Tel 401 732 0667 Fax 401 732 0590 www viessmann us com info viessmann us com 12 5167 513 v1 4 Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper ...

Reviews: