27
Troubleshooting
Diagnostics
Faults with fault display at the display and programming unit
General process error
Fault
code
System
characteristics
Cause
Remedy
20
Fan does not stop
during the air
pressure switch
idle state check
Wind influence on
fan
Check flue gas draught
(chimney)
Air pressure switch
contact does not
open
Air pressure switch
faulty
Replace air pressure
switch
21
Air pressure switch
does not signal air
pressure, fan does
not run
Air pressure switch
faulty
Replace air pressure
switch
Fan does not run
Fan faulty, cables
faulty or broken
Check cables and replace
fan, if required
22
Gas governor does
not signal gas
pressure
Gas shut−off valve
closed, gas
governor faulty
Open gas shut−off valve,
check gas supply
pressure and clean gas
filter, if necessary
25
No flame after
safety time,
ionisation flame
Ionisation electrode
incorrectly adjusted
Adjust ionisation
electrode (see page15)
y
ionisation flame
monitor signals no
flame
Ignition electrodes
incorrectly adjusted
Adjust ignition
electrodes (see page15)
Insulation body of
ignition electrodes
cracked
Replace ignition
electrodes
Incorrect gas type
selected
Adjust gas type (see
page7)
Gas combination
valve does not
open
Check gas combination
valve and replace it, if
required
Combustion
characteristics not
ideal
Adjust burner (see
page11 and 12)
Parameter set
incorrectly adjusted
Adjust parameter set
(see page23 and 24)
5692541 GB
Summary of Contents for MatriX radiant burner
Page 35: ...35 Component summary Component summary 5692 541 GB B P N E O H K L M E F G A B C D...
Page 39: ...39 Parts list Parts list cont 5692 541 GB 006 007 003 002 036 036 035 036 009 001 5o 008 009...
Page 41: ...41 Appendix 5692 541 GB...
Page 43: ...43 Appendix Maint service Maint service Maint service Maint service 5692 541 GB...
Page 45: ...45 Appendix Maint service Maint service Maint service Maint service 5692 541 GB...
Page 47: ...47 Appendix Maint service Maint service Maint service Maint service 5692 541 GB...