Initial start−up, inspection and maintenance
Further details regarding the individual steps
(cont.)
Checking CO
2
content
1.
Open the gas shut−off valve.
2.
Start up the burner.
3.
Press keysS
E
and
D
simultaneously.
Please note:
Display
C
shows:
H
Status: d (=regular stop) and
H
Service: Level of modulation in
% (00.=100
%=full load,
00=0
%=partial load)
Full load
4.
Press+
F
until the service display
has incremented to 00. (=100
%).
5.
Measure the CO
2
content at the
flue pipe.
The CO
2
should be 8.8 to 9.3
%.
6
.
If the CO
2
content must be
changed,
H
remove cap
B
and
H
turn adjusting screw
A
(Allen
key 2.5mm) until the CO
2
content is within the stated
range:
Turning clockwise
³
CO
2
content drops,
Turning anti−clockwise
³
CO
2
content rises.
5692541 GB
C
D
E
F
A
B