![Viessmann MatriX radiant burner Service Instructions Manual Download Page 12](http://html1.mh-extra.com/html/viessmann/matrix-radiant-burner/matrix-radiant-burner_service-instructions-manual_1017538012.webp)
12
Initial start−up, inspection and maintenance
Further details regarding the individual steps
(cont.)
Partial load
7.
Press key
D
, until the service
display has decremented to 00
(partial load).
8.
Measure the CO
2
content at the
flue pipe.
The CO
2
should be 8.8 to 9.3
%.
9.
If the CO
2
content must be
changed,
H
Unscrew cover
B
and
H
turn adjusting screw
A
in
small steps (Torx40) until the
CO
2
content is within the stated
range.
10.
Record the actual values in the
service report (from page42).
11.
Press+
F
until the
service display shows 00.
(=100
%).
12.
Measure the CO
2
content.
Repeat step6, if the value is not
8.8 to 9.3
%.
13.
Record the actual values in the
service report (from page42).
14.
Press keysS
E
and
D
simultaneously.
Burner is now in operating mode.
5692541 GB
C
D
E
F
B
A
Summary of Contents for MatriX radiant burner
Page 35: ...35 Component summary Component summary 5692 541 GB B P N E O H K L M E F G A B C D...
Page 39: ...39 Parts list Parts list cont 5692 541 GB 006 007 003 002 036 036 035 036 009 001 5o 008 009...
Page 41: ...41 Appendix 5692 541 GB...
Page 43: ...43 Appendix Maint service Maint service Maint service Maint service 5692 541 GB...
Page 45: ...45 Appendix Maint service Maint service Maint service Maint service 5692 541 GB...
Page 47: ...47 Appendix Maint service Maint service Maint service Maint service 5692 541 GB...