Control system (BMS 2007)
22
CHP switching cabinet
VITOBLOC 200
5780078
GB
Data item list CHP UNI 001
Analog values from the analog box
address length designation
type
exp.
unit
40
2
NiCr-Ni / 1 temperature A
I16
0
°C
42
2
NiCr-Ni / 2 temperature B
I16
0
°C
44
2
NiCr-Ni / 3 temperature C
I16
0
°C
46
2
NiCr-Ni / 4 temperature D
I16
0
°C
48
2
PT100/1 cooling water
I16
-1
°C
50
2
PT100/2 heating water return
I16
-1
°C
52
2
PT100/3 heating water
I16
-1
°C
54
2
PT100/4 oil temperature
I16
-1
°C
56
2
PT100/5 mixed temperature
I16
-1
°C
58
2
PT100/6 mixed cooling water temperature
I16
-1
°C
60
2
battery voltage
I16
-1
V
62
2
oil pressure
I16
-1
bar
64
2
lambda probe voltage
I16
-1
mV
66
2
spare
-
-
-
68
2
spare
-
-
-
70
2
spare
-
-
-
72
2
spare
-
-
-
74
2
speed
U16
0
rpm
76
2
temperature controller
I16
-1
°C
78
2
temperature release
I16
-1
°C
line protection
address length designation
type
exp.
unit
80
2
mains voltage L1
I16
0
V
82
2
mains voltage L2
I16
0
V
84
2
mains voltage L3
I16
0
V
86
2
alternator voltage L1
I16
0
V
88
2
alternator voltage L2
I16
0
V
90
2
alternator voltage L3
I16
0
V
92
2
alternator current L1
I16
0
A
94
2
alternator current L2
I16
0
A
96
2
alternator current L3
I16
0
A
98
2
total mains voltage
I16
0
V
100
2
total alternator voltage
I16
0
V
102
2
total alternator current
I16
0
A
104
2
output
I16
0
kW
106
4
network frequency
F32
0
Hz
110
4
alternator frequency
F32
0
Hz
114
2
spare
-
-
-
116
2
spare
-
-
-
118
2
CosPhi
I16
-3
-
120
4
spare
U32
0
kWh
124
16
spare
-
-
-
Tab. 25 Data item list, Part 3
– analog values and line protection