Control system (BMS 2007)
VITOBLOC 200
CHP switching cabinet
23
5780078
GB
List of fault messages
message
byte
bit
designation
comment
0
0
7
1
0
6
emergency stop
2
0
5
minimum oil level
3
0
4
minimum cooling water pressure
4
0
3
minimum gas pressure
5
0
2
safety temperature
6
0
1
alternator temperature
7
0
0
sound hood temperature
8
1
7
ventilator malfunctioning
9
1
6
cooling water pump malfunctioning
10
1
5
maximum exhaust gas
counterpressure
11
1
4
feed switch
12
1
3
external malfunction
13
1
2
overspeed
14
1
1
cooling water temperature
15
1
0
maximum exhaust gas temperature
16
2
7
minimum exhaust gas temperature
17
2
6
minimum oil pressure
18
2
5
maximum gas pressure
19
2
4
heating water pump malfunctioning
20
2
3
starting speed < 50 Upm
21
2
2
ignition speed
22
2
1
speed range
23
2
0
speed < 1,200 Upm
24
3
7
enabling malfunctioning
25
3
6
synchronising malfunctioning
26
3
5
speed < 50 / pick-up
27
3
4
maximum oil level
28
3
3
maximum temperature Pt100_2
from V.49
29
3
2
maximum temperature Pt100_3
from V.49
30
3
1
maximum output
31
3
0
reverse power
32
4
7
power regulator malfunctioning
33
4
6
lambda regulator malfunctioning
34
4
5
alternator contact malfunctioning
35
4
4
ignition malfunctioning
36
4
3
oil pressure malfunctioning
37
4
2
lambda starting position
38
4
1
knocking ON
39
4
0
knocking OFF
40
5
7
timer deselect
message
41
5
6
timer release
message
42
5
5
network breakdown F <
warning
43
5
4
network breakdown F >
warning
44
5
3
network breakdown U+F <>
warning
45
5
2
minimum knocking output