12
4x
M10x30
A
B
C
Fig. 7
Burners 120 - 318 kW
A
Gas connection
B
Ventilation air connection
C
Venturi extension for burners from 200 kW for
open flue
operation (in separate box)
!
Please note
Mechanical damage to delicate components will
impair the burner function.
Exercise great care when inserting the burner
into the combustion chamber. The burner gauze
assembly, electrodes and insulation block must
not be damaged.
Insert the burner. Secure screws by hand. Tighten the
screws diagonally with a torque of 10 Nm.
Mounting the burner
(cont.)
5814780