42
Rated heating output range
TF/TR = 50/30
kW
16 - 80 32 - 120 32 - 160 48 - 200 48 - 240 64 - 280
64 - 318
TF/TR = 80/60
kW
15 - 74 29 - 110 29 - 146 44 - 184 44 - 220 58 - 258
58 - 291
Weight
Overall unit weight
kg
238
295
295
340
340
385
385
Packed unit
kg
288
345
345
390
390
435
435
Boiler body
kg
183
230
230
265
265
300
300
Boiler body with transport
pallet
kg
210
260
260
295
295
330
330
Burner
kg
10
11
11
15
15
15
15
Water capacity
l
65
103
103
145
145
180
180
Connections
Boiler flow
PN 6 DN
50
50
50
65
65
65
65
Boiler return
PN 6 DN
50
50
50
65
65
65
65
Safety connection
R
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Drain
R
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
1
¼
Trap with condensate drain
mm
20
20
20
20
20
20
20
Flue gas parameters
*2
Temperature (at a return tem-
perature of 30 °C)
■
At rated heating output
°C
45
45
45
45
45
45
45
■
At partial load
°C
35
35
35
35
35
35
35
Temperature (at a return tem-
perature of 60 °C)
°C
65
65
65
65
65
65
65
Mass flow rate (for natural
gas)
■
At rated heating output
kg/h
120
180
240
300
360
420
477
■
At partial load
kg/h
36
54
72
90
108
126
143
Flue gas connection
DN
200
200
200
200
200
200
200
Draught at
mbar
0.7
0.7
0.7
0.7
0.7
0.7
0.7
flue outlet
Pa
70
70
70
70
70
70
70
Product parameters ac-
cording to EnEV
Standard seasonal efficien-
cy [to DIN]
For heating system tempera-
ture 40/30 °C
%
Up to 98 (Hs) [gross cv] / 109 (Hi) [net cv]
For heating system tempera-
ture 75/60 °C
%
Up to 96 (Hs) [gross cv] / 106 (Hi) [net cv]
Standby loss qB,70
%
0.6
0.5
0.3
0.6
0.6
0.6
0.6
NOx
NOx class 6, < 56 mg/kWh
*2
Values for calculating the size of the flue system to EN 13384, based on 10 % CO
2
for natural gas
Flue gas temperatures as actual gross values at 20 °C combustion air temperature.
The details for partial load refer to an output of 30 % of the rated heating output. If the partial load differs (subject to burner
operating mode), calculate the flue gas mass flow rate accordingly.
Specification
(cont.)
5814780