Functions
Operating conditions
(cont.)
Time switch
Preconditions: "Time switch Yes" must be configured (see pageĂ12).
In the time switch program, two different switching periods can be set for
each weekday.
Each switching period requires the input of a switch-on and a switch-off point.
Within the switching period, the control unit operates in standard mode;
outside the period it operates in reduced mode.
Time switch
(multi-boiler control unit)
Example:
For Tuesday, the switching periods 8 to 16 and 20
to 22Ăhrs standard mode have been set up.
In the "Operating details" menu (see pageĂ15) you can scan whether the
control unit is set to "Standard mode" or "Reduced mode" on account of the
time switch program.
Holiday program
Preconditions: "Holiday mode Yes" must be configured (see pageĂ12).
Eight different holiday periods with start and end times may be set up in the
holiday program.
Holiday program
(multi-boiler control unit)
The holiday period begins on 16.07.03 and ends
on 15.08.03.
Please note:
Set room temperatures during the holiday period
can be adjusted in the "Set values" menu (see
pageĂ16).
In the "Operating details" menu (see pageĂ15) you can scan whether the
control unit is set to "Time program holiday mode".
5862Ă474ĂGB
Tu 08:00 Ć 16:00
20:00 Ć 22:00
1: 16Ć07Ć2003
up to 15Ć08Ć2003