Control
Initial start-up/configuration
(cont.)
Multi-boiler control unit
Preconditions: Operating levelĂ3
must
be selected (see pageĂ10).
Select "Multi-boiler control unit" with , if
"Multi-boiler control unit" is not already
displayed; confirm with .
Select "Configuration" with ; confirm with .
Select "Yes" with / ; confirm with .
Outside temperature sensor
Select "Yes" if an outside temperature sensor is
connected to the control unit.
Frost protection
Preconditions: "Outside sensor Yes" must be
configured.
Select "Yes" if the flow temperature should not fall
below an adjustable minimum temperature from a
certain outside temperature on.
Time switch
Preconditions: "Outside sensor Yes" must be
configured.
Select "Yes" if the control unit should be
operated with the integral time switch, i.e.
switching periods can be set up (see pageĂ18).
Holiday program
Preconditions: "Time switch Yes" must be
configured.
Select "Yes", if operation with a holiday program is
required (see pageĂ18).
5862Ă474ĂGB
Control unit 001ĆB
multi-boiler system
Configuration
Configuration
Yes
Outside sensor
Yes
Frost protection
outside temp. Yes
Time switch
Yes
Holiday program
Yes