39
Note
■
The control circuit must be supplied with power
with-
out
blocking by the power supply utility, so a sepa-
rate power supply is required for the control circuit.
■
A separate power supply for the control circuit
necessitates a change to the internal wiring. This
may only be carried out by an electrical contractor
according to the connection diagram.
■
The control circuit power supply and the cable for the
power-OFF signal can be combined in a single 5-
core cable.
Cable lengths in the heat pump plus wall clearance
Control circuit power supply (230 V~ if on
site)
3 m
Power circuit power supply (400V~)
3 m
Additional connecting cables
2 m
Power supply with power-OFF
Power-OFF without on-site load disconnection (delivered condition)
The power-OFF signal is connected directly to the heat
pump control unit via floating contact. The compres-
sors are shut down when power-OFF is enabled.
Note
Observe the technical connection conditions of the rel-
evant power supply utility.
Electronic soft starter, type SMC
Electronic soft starter functions:
■
Monitoring the compressor mains feed
■
Reducing the compressor starting current during the
starting procedure
Delivered condition:
■
Rotating field, phase asymmetry: 20 %
■
Max. operating current of "Imax" compressor:
dependent on compressor output
Overload protection
If the tolerance ranges of the electronic soft starter are
exceeded, the soft starter will automatically separate
the appliance from the mains.
Remove the cause if the relay has responded. The
relay does not need to be reset.
Starting characteristics
The starting characteristics are set at the DIP switches
behind the transparent protective flap of the electronic
soft starter. At the factory, the DIP switches are set to
suit the respective heat pump type.
Prior to commissioning, compare the DIP switch set-
tings with the details in the separate "Connection and
wiring diagram", and adjust if necessary.
Installation sequence
Power supply
(cont.)
5789 986 GB
Installation