32
3.
Disconnect corrugated hose
C
from lute
D
.
4.
Turn lute, tilt slightly and pull downwards.
5.
Fill the lute with water.
6.
Refit lute
D
and push on corrugated hose
C
.
!
Please note
To prevent water escaping when installing
the lute, seal off the condensate drain open-
ing with your thumb.
7.
Reassemble the trap in reverse order.
8.
Check that the condensate pipe is connected cor-
rectly to the trap and heat exchanger.
Note
Route the drain hose without any bends and with a
constant fall.
9.
Fit cover panel and secure control unit back in its
operating position.
Venting the heating system
A
Fig. 24
1.
Close the gas shut-off valve and switch the control
unit ON.
2.
Check whether the air vent screw in quick-action
air vent valve
A
of the heating circuit pump is
open.
3.
Activate venting function (see following steps).
Note
For function and sequence of the venting function,
see page 32.
4.
Check the system pressure.
5.
Open the gas shut-off valve.
Activating the venting function
Tap the following buttons:
1. "Menu"
2. "Service"
3.
Enter
"viservice"
password.
4. "Service functions"
5. "Air vent valve"
6.
Activate the venting function with
"Yes"
.
The venting function ends automatically after
20 min or when you tap OK.
Commissioning, inspection, maintenance
Filling the trap with water
(cont.)
5789 302 GB