35
G
B
D
C
E
4x
F
F
A
Fig. 26
1.
Switch OFF the power supply and the ON/OFF
switch at the control unit.
2.
Close the gas shut-off valve and safeguard against
reopening.
3.
Remove cables from fan motor
A
, gas train
B
,
ignition and ionisation electrode
C
, ignition unit
D
and earth tab
E
.
4.
Undo gas supply pipe fitting
F
.
5.
Undo four screws
G
and remove the burner.
!
Please note
Prevent damage to the burner.
Never rest the burner on the burner gauze
assembly.
Commissioning, inspection, maintenance
Removing the burner